PROGRAMMING OF THE HOURS COUNTER (

SET   HR_

)

 

The hour counter will be increased when the measure of the parameter will exceed the set threshold value. 

 

ELM-4D1P 

instruction manual

IM443-U v0.7 

pag. 12

 

seT  UP  

Æ

 

seT  Up 

RESET 
SET   DO1 
SET   DO2 
SET   AN   OUT 
SET   HR_ 
--- OFF   OFF  

(the visualization depends on the settings and the I/O status) 

 

HR_ SEl  VLN 
HR_ SEl  AMP 
HR_ SEl  AN 
HR_ SEl  P.f  

To chose the parameter 

HR_ SEl  ACT  

(see the variable list) 

HR_ SEl  REA 
HR_ SEl  APP 
HR_ SEl  VLL 
HR_  SEL  FRE 
HR_  sel T

°

 

Set the threshold 

Increase 

HR_  HI  

Decrease 

Confirm and end of hour counter settings.

 

SELECT THE PARAMETER TO LINK TO THE HOURS COUNTER 
From the previous setting, pressing the 

key it’s possible to set the hours counter: the message SET   HR_ appears 

on the 

display. Press the 

key to define the parameter to link to the hours counter. Press more time the 

key to 

select the parameter and the 

key to confirm it. 

SET THE THRESHOLD 
Subsequently it’s necessary to set the threshold using the 

(to increase) and 

(to decrease) keys. Confirm with 

A

 

key. 

 

I/O INFO PAGE 

After the hour counter set, the I/O info page appears in 

F

 displays: on the first part (L1) appear “ do_” indication, on 

the second part (L2) the status of the first digital output (DO1), on the third part (L3) the status of the second digital 
output (DO2). 
The status of the two digital outputs is ON if the digital output is activated or OFF if deactivated. 
The status of the serial port appear on the 

G

 display when the instrument has this option. If the instrument receives 

data, it displays the letter R and the number of the instrument that is in communication while if the instrument 
transmits data, it displays the letter T. 
 

 

VARIABLE LIST

 

VLN      three-phase voltage 
AMP        three-phase current 
AN          neutral current 
P.F          three-phase power factor 
ACT  

active power 

REA  

reactive power 

APP  apparent 

power 

VLL       phase to phase voltage 
FRE        frequency 
T

°

C         temperature 

Содержание ELM-4D1P

Страница 1: ...485 and with analog output OPTIONS Power Supply 20 60 Vac 24 72 Vcc C1 Power Supply 85 230 Vac 90 250 Vcc C2 Insulated current inputs T MEASURED PARAMETERS parameters unit of measurement initial ident...

Страница 2: ...Vac dc version Terminals Power Supply Terminals Power Supply Terminals Power Supply 19 20 0 110V 100 125Vac 50 60Hz 19 21 0 230V 220 240Vac 50 60Hz 19 23 0 400V 380 415Vac 50 60Hz 19 21 20 60Vac 24 7...

Страница 3: ...WIRING DIAGRAMS W ELM 4D1P instruction manual IM443 U v0 7 pag 3...

Страница 4: ...internalCT S1 I1 S2 auxiliary power supply S1 I2 S2 S1 ELM I3 S2 VL1 VL2 VL3 N with Ineutral option In VL1 VL2 VL3 N L1 S1 L2 P1 L3 S1 S2 L1 L2 L3 S1 S2 N P1 P2 P1 P2 CT connection to Voltage insertio...

Страница 5: ...lay indicates also the values of the active and reactive energy counters Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical m...

Страница 6: ...ynchronism 50 type 60 version with digital output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase f...

Страница 7: ...of the CT rate will be possible to set this value example with CT 1000 5the value will be 200 Pressing the A key confirm and go away with the next setting Programming of the average time seT AVG T Aft...

Страница 8: ...e password is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instrument at the enter of the set...

Страница 9: ...tput will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the...

Страница 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Страница 11: ...ing the C key the message SET AN OUT will appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will...

Страница 12: ...key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO P...

Страница 13: ...the measures appear on the L1 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltage va...

Страница 14: ...er maximum three phase powers max maxD avg I L1 max avg I L2 max avg I L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg W max avg...

Страница 15: ...electrically disturbed it is suggested to use 100 120ohm 1 2W resistors placed between the common of the RS485 outlet and the shielded cable For other information on the serial line it s better to se...

Страница 16: ...auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse P...

Отзывы: