SET GENERAL PARAMETER (
SET UP
)
Entry to menu:
seT UP
Æ
seT Up
RESET
SET DO1
SET DO2
SET AN OUT
SET HR_
ELM-4D1P
instruction manual
IM443-U v0.7
pag. 6
DO_ OFF OFF
SET CT
Increase
Set CT ratio
from 1 to 2000
Decrease
SET VT
Increase
Set VT ratio
from 0.1 to 400.0
Decrease
(version with A
n
input) SET
CTN
Increase
Set CT ratio of the neutral
input
from 1 a 2000
Decrease
seT AV9 T
Increase
Set average time
from 1 to 30 minutes
Decrease
seT EN TB1 TB2
Set Energy visualization
TOT PAR
type
NORMAL
seT 3pH BALANC
Set connection
UN_BAL
type
1PH L1
seT MDE -3-
Set wiring connection
type
-4-
seT SYN MDE L1
Set synchronism
50
type
60
(version with digital output)
seT PUL SE
10.0
kW-kVAr / pulse
Set pulse weight
01.0
kW-kVAr / pulse
0.10
kW-kVAr / pulse
0.01
kW-kVAr / pulse
(version with digital output)
seT TPL
Increase
from 100 to 500 mS
in step by 100 mS
Decrease
(version with serial output)
seT ID ADR
Increase
Set address of network
from
001
to
247
Decrease
seT SER BDR
Set baud rate
19200 baud
19.2
serial interface
9600 baud
9.60
(version
with serial output
)
4800 baud
4.80
2400 baud
2.40
seT PAR
Set parameters of bit: 8data 1stop-no parity
8.1 paR NO
Communication
bit: 8data 2stop-no parity
8.2 paR NO
serial interface bit: 8data 1stop-even parity
8.1 paR EVE
(version with serial output)
bit: 8data 1stop-odd parity
8.1 paR ODD
SET PAS
Increase
Set Password
OFF - 0002 ÷ 9999
Decrease
Confirm and end of general settings