SET GENERAL PARAMETER (

SET   UP

)

 

Entry to menu: 

seT  UP  

Æ

 

seT  Up 

RESET 
SET   DO1 
SET   DO2 
SET   AN   OUT 
SET   HR_ 

ELM-4D1P 

instruction manual

IM443-U v0.7 

pag. 6

 

DO_   OFF   OFF 

SET   CT                                                 

Increase

 

Set CT ratio

 

from 1 to 2000                           

Decrease

 

 

SET   VT                                                 

Increase

 

Set VT ratio

 

from 0.1  to 400.0                       

Decrease

 

 

(version with A

input) SET 

 

CTN 

 

Increase

 

Set CT ratio of the neutral

 

input 

from 1 a 2000                     

Decrease

 

 

seT AV9 T                                         

Increase

 

Set average time

 

from 1 to 30 minutes                            

Decrease

 

 

seT  EN                                                 TB1  TB2 

Set Energy visualization                      

TOT   PAR 

type                                                        

NORMAL 

 

seT 3pH                                   BALANC 

Set connection                                     

UN_BAL 

type                                                        

1PH   L1 

seT  MDE                                              -3- 

Set wiring connection

 

type                                                        

-4- 

 

seT SYN MDE                                    L1 

Set synchronism                                  

50 

type                                                        

60 

 

(version with digital output) 

seT  PUL   SE  

10.0 

kW-kVAr / pulse

 

Set pulse weight                                   

01.0 

kW-kVAr / pulse

 

0.10 

kW-kVAr / pulse

 

0.01 

kW-kVAr / pulse

 

 

(version with digital output) 

seT  TPL  

Increase

 

from 100 to 500 mS 
in step by 100 mS                                  

Decrease

 

(version with serial output) 

seT  ID  ADR  

Increase

 

Set address of network

 

from 

001 

to 

247                         

Decrease

 

 

seT  SER  BDR 

Set baud rate 

 

19200 baud 

 

19.2 

serial interface 

9600 baud 

9.60 

(version 

with serial output

)  

4800 baud 

 

4.80 

2400 baud                                              

2.40 

 

seT  PAR 

Set parameters of          bit: 8data 1stop-no parity                    

8.1   paR  NO 

Communication 

bit: 8data 2stop-no parity                    

8.2   paR NO 

serial interface               bit: 8data 1stop-even parity                

8.1   paR  EVE 

(version with serial output) 

bit: 8data 1stop-odd parity 

8.1   paR  ODD 

 

SET   PAS                                              

Increase

 

Set Password

 

OFF   - 0002 ÷ 9999                 

Decrease

 

 

Confirm and end of general settings

 

Содержание ELM-4D1P

Страница 1: ...485 and with analog output OPTIONS Power Supply 20 60 Vac 24 72 Vcc C1 Power Supply 85 230 Vac 90 250 Vcc C2 Insulated current inputs T MEASURED PARAMETERS parameters unit of measurement initial ident...

Страница 2: ...Vac dc version Terminals Power Supply Terminals Power Supply Terminals Power Supply 19 20 0 110V 100 125Vac 50 60Hz 19 21 0 230V 220 240Vac 50 60Hz 19 23 0 400V 380 415Vac 50 60Hz 19 21 20 60Vac 24 7...

Страница 3: ...WIRING DIAGRAMS W ELM 4D1P instruction manual IM443 U v0 7 pag 3...

Страница 4: ...internalCT S1 I1 S2 auxiliary power supply S1 I2 S2 S1 ELM I3 S2 VL1 VL2 VL3 N with Ineutral option In VL1 VL2 VL3 N L1 S1 L2 P1 L3 S1 S2 L1 L2 L3 S1 S2 N P1 P2 P1 P2 CT connection to Voltage insertio...

Страница 5: ...lay indicates also the values of the active and reactive energy counters Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical m...

Страница 6: ...ynchronism 50 type 60 version with digital output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase f...

Страница 7: ...of the CT rate will be possible to set this value example with CT 1000 5the value will be 200 Pressing the A key confirm and go away with the next setting Programming of the average time seT AVG T Aft...

Страница 8: ...e password is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instrument at the enter of the set...

Страница 9: ...tput will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the...

Страница 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Страница 11: ...ing the C key the message SET AN OUT will appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will...

Страница 12: ...key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO P...

Страница 13: ...the measures appear on the L1 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltage va...

Страница 14: ...er maximum three phase powers max maxD avg I L1 max avg I L2 max avg I L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg W max avg...

Страница 15: ...electrically disturbed it is suggested to use 100 120ohm 1 2W resistors placed between the common of the RS485 outlet and the shielded cable For other information on the serial line it s better to se...

Страница 16: ...auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse P...

Отзывы: