elco ELM-4D1P Скачать руководство пользователя страница 16

TECHNICAL FEATURES

 

MEASURES, PRECISIONS

 

voltage

 

true RMS of the phase voltages and the phase to phase voltages and values of three phase system 
range of total measure: 20÷500V trms phase-phase - 290V rms phase-neutral 
visualization (0,02÷50,0kV)  -  measure precision: ±0,5% ±1 digit– management maximum values

current

 

true RMS of the phase currents and of the value of three phase system 
range of measure: 0,02÷5A trms   -  measure precision: ±0,5% ±1 digit 
visualization 0,02÷9990A

 

frequency

 

frequency of the L1 phase –range of measure: 40÷500Hz 
precision: ±0,5% ±1 digit

 

powers

 

phase and three phase system apparent, reactive and active power 
range of measure: 0,001÷9990kW - 0,001÷9990kVAr - 0,001÷9990kVA 
precision: ±1% ±1 digit

 

power factor

 

phase and three phase power factor 
range of measure: -0,1÷0,1 / precision: ±1% ±1 digit

energy measure

 

three phase system apparent, active and reactive energy 
range of measure:  0÷99999999,9 kWh / kVArh 

class 2 ( IEC 1036) 

precision: ±1

 

hours counters

 

precision: ±1%; risolution 1/10 of hour

 

AUXILIARY POWER SUPPLY, INPUTS

 

auxiliary power 
supply

 

Version Vac: 100-125V / 220-240V / 380-415V ±10% - frequency 50-60Hz 
Version Vca/dc: 20-60Vac – 24-72Vdc 
Version Vca/dc: 80-230Vac – 90-250Vdc 
consumption max 4VA

 

voltage inputs

 

from 20 to 500V phase-phase; permanent ov20% -  input impedance:  1 M

Ω 

insertion on three phase line with 3 wires, 4 wires and single phase 
insertion in MT with external TV and transforming rate programmable from 1 to 400

 

current inputs

 

from 0,02 to 5A; permanent overload 30% - from external TA with secondary 5A, 
primary programmable from 5 to 10000A  -  auto-consumption <0,5VA

 

INPUTS / OUTPUTS

 

digital outputs

 

Two outputs with common, optomos 12÷230Vac/dc, max 150mA, 
insulation: 3kV for 60 seconds 
Pulse Function: 
Weight programmable 0,01-0,1-1-10 kWh/pulse 
Pulse duration 100-200-300 400 500 milliseconds selectable 
DO1: 

active energy pulse output (accumulated Tb1+Tb2) 

DO2: 

reactive energy pulse output (accumulated Tb1+Tb2)

 

analog output

 

Max load: 400

Ω  

Range 0-20mA; 4-20mA 
Insulation: 3kV for 60 Seconds

 

serial output

 

One optional output RS485, baud rate selectable, MODBUS-RTU protocol 
insulation: 3kV for 60 seconds

 

GENERAL

 

display, operators

 

4 displays with red LED 10mm everyone of 3 digit by 7 segments 
3 push-button for selecting measure and programming

mechanic

 

protection degree: IP52 frontal  -  IP20 enclosure and terminals  -  weight: about 0,5 kg 
connections with screw terminals for cable 2,5 mm

2

 

enclosure thermoplastic self-extinguishing  - for DIN rail mounting, 6 modules of 17,5mm

 

environmental

 

working temperature: -10÷60°C;  humidity <90% 
storing temperature: -25÷70°C 
insulation test: 3 kV for 1 minute

standards

 

EN 50081-2; EN 61000-6-2 
EN 61036-1; EN 61010-1

 

NOTE 
At reason of the evolution of standards and products, the company reserves to modify in every time  the features of the product described in this 
document, that it’s necessary to verify preventively. 
The liability of the producer for damage caused by defect of the product ”can be reduced or deleted (…) when the damage is caused joint by a 
defect of product or for blame of the damaged or a person of which the damaged is responsible” (Article 8, 85/374/CEE). 
 
 

 

 

 

Via Lago di Molveno, 20 – 36015 Schio (VI) 

Tel. +39 0445 661722 –Fax +39 0445 661792   

http://www.elco-italy.com

  

 

E-mail: 

[email protected]

[email protected]

  

 

ELM-4D1P 

instruction manual

IM443-U v0.7 

pag. 16

 

Содержание ELM-4D1P

Страница 1: ...485 and with analog output OPTIONS Power Supply 20 60 Vac 24 72 Vcc C1 Power Supply 85 230 Vac 90 250 Vcc C2 Insulated current inputs T MEASURED PARAMETERS parameters unit of measurement initial ident...

Страница 2: ...Vac dc version Terminals Power Supply Terminals Power Supply Terminals Power Supply 19 20 0 110V 100 125Vac 50 60Hz 19 21 0 230V 220 240Vac 50 60Hz 19 23 0 400V 380 415Vac 50 60Hz 19 21 20 60Vac 24 7...

Страница 3: ...WIRING DIAGRAMS W ELM 4D1P instruction manual IM443 U v0 7 pag 3...

Страница 4: ...internalCT S1 I1 S2 auxiliary power supply S1 I2 S2 S1 ELM I3 S2 VL1 VL2 VL3 N with Ineutral option In VL1 VL2 VL3 N L1 S1 L2 P1 L3 S1 S2 L1 L2 L3 S1 S2 N P1 P2 P1 P2 CT connection to Voltage insertio...

Страница 5: ...lay indicates also the values of the active and reactive energy counters Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical m...

Страница 6: ...ynchronism 50 type 60 version with digital output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase f...

Страница 7: ...of the CT rate will be possible to set this value example with CT 1000 5the value will be 200 Pressing the A key confirm and go away with the next setting Programming of the average time seT AVG T Aft...

Страница 8: ...e password is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instrument at the enter of the set...

Страница 9: ...tput will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the...

Страница 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Страница 11: ...ing the C key the message SET AN OUT will appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will...

Страница 12: ...key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO P...

Страница 13: ...the measures appear on the L1 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltage va...

Страница 14: ...er maximum three phase powers max maxD avg I L1 max avg I L2 max avg I L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg W max avg...

Страница 15: ...electrically disturbed it is suggested to use 100 120ohm 1 2W resistors placed between the common of the RS485 outlet and the shielded cable For other information on the serial line it s better to se...

Страница 16: ...auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse P...

Отзывы: