38
Parameters technician
Menu
Line no.
Selection possibilities
Unit
Min.
Max
Factory setting
Solid fuel boiler
4102
Lock other heat sources
Uit, Aan
Aan
4110
Setpoint min
°C
8
120
60
4130
Temp diff on
°C
1
40
8
4131
Temp diff off
°C
0
40
4
4133
Comparative temp
DHW sensor B3, DHW sensor B31,
Buffer sensor B4, Buffer sensor B41,
Flow temp setpoint, Setpoint min
Buffer sensor B41
4141
Excess heat discharge
°C
60
140
90
4170
Frost prot plant boiler pump
Off, On
On
Buffer
4720
Auto heat gen lock
-
None, with B4, with B4 and B42/B41
with B4
4721
Auto heat gen lock SD
°C
0
20
3
4722
Temp diff buffer/HC
°C
-20
20
-4
4724
Min st tank temp heat mode
°C
8
95
8
4750
Charging temp max
°C
8
95
80
4755
Recooling temp
°C
8
95
60
4756
Recooling DHW/HCs
-
Off, On
Off
4757
Recooling collector
-
Off, Summer, Always
Summer
4783
With solar integration
-
No, Yes
No
4790
Temp diff on return div
°C
0
40
10
4791
Temp diff off return div
°C
0
40
5
4795
Compar temp return div
-
With B4, With B41, With B42
With B4
4796
Optg action return diversion
-
Temperature decrease, Temp increase
Temp increase
4800
Partial charging setpoint
°C
8
95
60
4810
Full charging
-
Off, Heating mode, Always
Off
4811
Full charging temp min
°C
8
80
8
4813
Full charging sensor
-
With B4, With B42/B41
With B42/B41
DHW Storage tank
5010
Charging
-
Once/day, Several times/day
Several times/day
5020
Flow setpoint boost
°C
0
30
16
5021
Transfer boost
°C
0
30
8
5022
Type of charging
-
Recharging, Full charging, Full charging legio, Full
charg 1st time day, Full charg 1st time day legio
Recharging
5024
Switching diff
°C
0
20
5
5030
Charging time limitation
min
10
600
60
5040
Discharging protection
-
Off, Always, Automatic
Automatic
5050
Charging temp max
°C
8
95
70
5055
Recooling temp
°C
8
95
70
5056
Recooling heat gen/HCs
-
Off, On
Off
5057
Recooling collector
-
Off, Summer, Always
Always
5060
El imm heater optg mode
-
Substitute, Summer, Always
Substitute
5061
El immersion heater release
-
24h/day, DHW release, Time program 4/DHW
DHW release
5062
El immersion heater control
-
External thermostat, DHW sensor
DHW sensor
5070
Automatic push
-
Off, On
On
5085
Excess heat draw
-
Off, On
On
5090
With buffer
-
No, Yes
No
5092
With prim contr/system pump
-
No, Yes
No
5093
With solar integration
-
No, Yes
Yes
5101
Pump speed min
%
0
100
100
5102
Pump speed max
%
0
100
100
5130
Transfer strategy
-
Off, Always, DHW release
Always
5131
Comparison temp transfer
-
DHW sensor B3, DHW sensor B31
DHW sensor B3