35
Parameters technician
Menu
Line no.
Selection possibilities
Unit
Min.
Max
Factory setting
Domestic hot water
1600
Operating mode
-
Off, On, Eco
Off
1610
Nominal setpoint
°C
8
80
55
1612
Reduced setpoint
°C
8
80
40
1614
Nominal setpoint max
°C
8
80
65
1620
Release
-
24h/Day, Time programs HCs,
Time program 4/DHW
Time programs HCs
1630
Charging priority
-
Absolute, Shifting, None,
MC shifting PC absolute
MC shifting
PC absolute
1640
Legionella function
-
Off, Periodically, Fixed weekday
Off
1641
Legionella function periodically
-
1
7
7
1642
Legionella funct Day
-
Mo,Tu,We,Th,Fr,Sa,Su
Montag
1644
Legionella funct time
uu:mm
00:00
23:50
---
1645
Legionella funct setpoint
°C
55
95
65
1646
Legionella funct duration
min
10
360
30
1647
Legionella funct circ pump
-
Off, On
On
1660
Circulating pump release
-
Time program 3/HCP, DHW release,
Time program 4/DHW, Time program 5
DHW release
1661
Circulating pump cycling
-
Off, On
Off
1663
Circulation setpoint
°C
8
80
45
1680
Optg mode changeover
-
None, Off, On
None
Consumer circuit 1
1859
Flow temp setp cons request
°C
8
120
70
1874
DHW charging priority
-
No, Yes
Yes
1875
Excess heat draw
-
No, Yes
No
1878
With buffer
-
No, Yes
Yes
1880
With prim contr/system pump
-
No, Yes
Yes
Consumer circuit 2
1909
Flow temp setp cons request
°C
8
120
70
1924
DHW charging priority
-
No, Yes
Yes
1925
Excess heat draw
-
No, Yes
No
1928
With buffer
-
No, Yes
Yes
1930
With prim contr/system pump
-
No, Yes
Yes
Consumer circuit 3
1959
Flow temp setpoint
°C
8
45
1974
DHW charging priority
-
No, Yes
Yes
1975
Excess heat draw
-
No, Yes
No
1978
With buffer
-
No, Yes
Yes
1980
With prim contr/system pump
-
No, Yes
Yes
Swimming pool
2055
Pool setpoint solar heating
°C
8
80
26
2056
Pool setpoint producer heating
°C
8
80
22
2065
Pool charging priority solar
-
Priority 1, Priority 2, Priority 3
Priority 3
2070
Pool temperature maximum
°C
8
95
30
2080
Pool with solar
-
No, Yes
Yes
Primary control/
System pump
2110
Flow temp min limitation
°C
8
95
8
2111
Flow temp max limitation
°C
8
95
80
2121
Syst pump on heat gen lock
-
Off, On
Off
2130
Mixing valve boost
°C
0
50
5
2132
Actuator type
-
2-position, 3-position
3-position
2133
Switching differential 2-pos
°C
0
20
2
2134
Actuator running time
s
30
873
120
2135
P-Band (Xp
°C
1
100
32
2136
Integral action time (Tn) HC1
s
10
873
120
2150
Primary control/System pump
-
Upstream of buffer, Downstream of buffer
Downstream of buffer