Parameters technician
Basic display “Boiler temperature”
- Push OK button once
- Push Info button for 4 sec.
- Use the +- rotating button for selecting commissioning or technician level
- Push OK button once
- Use +- rotating button for selecting for instance “Drinking water menu”
- Push OK button once
- Use the +- rotating button, for instance in the drinking water menu, for selecting
“Parameter no. 1612 - Reduced target value”
- Push OK button once
- Use +- rotating button to change the currently set value
- Push OK button once -> the value is stored
- Push 2 x ESC to return to the basic display “Boiler temperature”
Menu
Line no.
Selection possibilities
Unit
Min.
Max
Factory setting
Time of day
and date
1
Hours / Minutes
hh:mm
00:00
23.59
--.--
2
Day / Month
dd:mm
01.01
31.12.
--.--
3
Year
yyyy
2004
2099
--.--
5
Start of summertime Day / Month
dd:mm
01.01
31.12.
25.03.
6
End of summertime Day / Month
dd:mm
01.01
31.12.
25.10.
Operator
section
20
Language
-
English, German, French, Italian, Danish,
Dutch, Spanish, Czech, Slovenian, Turkish
German
22
Info
-
Temporarily, Permanently
Temporarily
26
Operation lock
-
Off, On
Off
27
Programming lock
-
Off, On
Off
28
Direct adjustment
-
Automatic storage, Storage with confirmation
Storage with confirmation
44
Operation HC2
-
Jointly with HC1, Independently
Jointly with HC1
46
Operation HC3/P
-
Jointly with HC1, Independently
Jointly with HC1
70
Software Version
-
0
99.0
Indication only
Time program
HC 1
500
Preselection
-
Mo-Su, Mo-Fr, Sa-Su
Mo-Su
501
Mo-Su: 1. Phase On
hh:mm
00:00
00:00
06:00
502
Mo-Su: 1. Phase Off
hh:mm
00:00
00:00
22:00
503
Mo-Su: 2. Phase On
hh:mm
00:00
00:00
--.--
504
Mo-Su: 2. Phase Off
hh:mm
00:00
00:00
--.--
505
Mo-Su: 3. Phase On
hh:mm
00:00
00:00
--.--
506
Mo-Su: 3. Phase Off
hh:mm
00:00
00:00
--.--
516
Default values
-
Yes, No
No
Time program
HC 2
(when
activated)
520
Preselection
-
Mo-Su, Mo-Fr, Sa-Su
Mo-Su
521
Mo-Su: 1. Phase On
hh:mm
00:00
00:00
06:00
522
Mo-Su: 1. Phase Off
hh:mm
00:00
00:00
22:00
523
Mo-Su: 2. Phase On
hh:mm
00:00
00:00
--.--
524
Mo-Su: 2. Phase Off
hh:mm
00:00
00:00
--.--
525
Mo-Su: 3. Phase On
hh:mm
00:00
00:00
--.--
526
Mo-Su: 3. Phase Off
hh:mm
00:00
00:00
--.--
536
Default values
-
Yes, No
No
Time program
HC3/P
540
Preselection
-
Mo-Su, Mo-Fr, Sa-Su
Mo-Su
541
Mo-Su: 1. Phase On
hh:mm
00:00
00:00
06:00
542
Mo-Su: 1. Phase Off
hh:mm
00:00
00:00
22:00
543
Mo-Su: 2. Phase On
hh:mm
00:00
00:00
--.--
544
Mo-Su: 2. Phase Off
hh:mm
00:00
00:00
--.--
545
Mo-Su: 3. Phase On
hh:mm
00:00
00:00
--.--
546
Mo-Su: 3. Phase Off
hh:mm
00:00
00:00
--.--
556
Default values
-
Yes, No
No
Time program
4 DHW
560
Preselection
-
Mo-Su, Mo-Fr, Sa-Su
Mo-Su
561
Mo-Su: 1. Phase On
hh:mm
00:00
00:00
06:00
562
Mo-Su: 1. Phase Off
hh:mm
00:00
00:00
22:00
563
Mo-Su: 2. Phase On
hh:mm
00:00
00:00
--.--
564
Mo-Su: 2. Phase Off
hh:mm
00:00
00:00
--.--
565
Mo-Su: 3. Phase On
hh:mm
00:00
00:00
--.--
566
Mo-Su: 3. Phase Off
hh:mm
00:00
00:00
--.--
576
Default values
-
Yes, No
No
Overview of commissioning
parameters
The parameter lines with a grey
background only become visible at the
commissioning level.
The complete parameter list becomes
visible at the technician level.