16
Collector panel hydraulics
max. 120 tubes
Vertical installation
Diagonal connecting pipes:
A maximum of 120 tubes (12 m² ab-
sorber surface) can be connected to-
gether in a collector panel array.
The minimum flow shall not fall below
30 l/m²h (caution when using variable
speed pumps).
Installations with more than 120 tubes
(12 m² absorber surface) shall be con-
nected in parallel based on the Tichel-
mann principle. The minimum flow shall
not fall below 30 l/m²h per Tichelmann
circuit (caution when using variable
speed pumps).
Interconnecting pipe on one side
only
A maximum of 60 tubes (6 m² absorber
surface) can be interconnected in a
collector panel array when intercon-
nected on one side only.
The minimum flow shall not fall below
45 l/m²h (caution when using variable
speed pumps).
When interconnected on one side only,
installations with more than 60 tubes (6
m²) shall be connected in parallel
based on the Tichelmann principle.
The minimum flow shall not fall below
45 l/m²h per Tichelmann circuit (caution
when using variable speed pumps).
max. 120 tubes
max. 60 tubes
max. 60 tubes