Fuses description.
F1 - 20A 250V
Output battery protection fuse (27 - 28).
F2 - 20A 250V
Transformer output 24VAC protection fuse.
FR1 - 0,5A 250V
Main power supply 230VAC self-repairing protection fuse
(non-replaceable)
.
FR2 - 1,6A 250V
Self-repairing protection fuse for photocells, electro-lock, flashing light and accessories
(non-replaceable)
.
WARNING: High risk of electric shock!
Cut off the main power supply from the panel before touching the fuses (F1 and
F2).
We recommend to re-check the wiring before replacing any fuse
7
Remote control storing (recommended to be done with the antenna disconnected).
As START button:
1) Close the gate. Press once the button PROGR; led DL6 starts flashing.
2) Press the remote control button you want to store; led DL6 switched off as confirmation that code has been stored.
You can store up to max. 32 different codes for the Start.
As Pedestrian button:
1) Close the gate. Press twice the button PROGR; led DL6 starts flashing.
2) Press the remote control button you want to store; led DL6 switched off as confirmation that code has been stored.
You can store up to max. 32 different codes for the Pedestrian.
8
Remote control cancellation.
Cancellation of a single code stored into START or PEDESTRIAN:
1) Press at the same time both buttons PROGR and PAUSA; led DL6 starts flashing quickly.
2) Within 10 sec. press remote control button you want to cancel; led DL6 switches off to confirm the cancellation.
Cancellation of all codes stored into the control panel:
Press at the same time both buttons PROGR and PAUSA for about 10 seconds.
Led DL6 starts flashing quickly and after 10 seconds will switch off confirming the cancellation has been done.
9
Preliminary checks before setting the control panel.
1) Power the control panel and verify that LED Stop, Foto, Foto AP and Costa are on; if this doesn’t correspond, re-check
the wirings and or safety devices state. Any NC contact not used, has to be wired/closed.
2) Verify that all safety devices installed in the gate are working properly in order to reduce any possible accident.
3) Verify the correct wirings, keeping in mind that 1
st
START impulse has to open the gate, otherwise, just swap the wires
17-18 for M1 and/or 19-20 for M2.