Pellet burner GP xx sc 40
Table 7.2. Description of the failures, saved in the “LOG” menu of the pellet burner’s from
series „GP xx sc” controller.
ERROR
CODE
INSCRIPTION
DISPLAYED ON THE
DISPLAY
ERROR DESCRIPTION
REMEDY
10
[ERROR: IGNITION]
[FAILED]
Ignition failed
Clean the burner grate.
Check the availability of
fuel.
Seek advice from a service
technician.
11
N/A
Loss of flame during burner
operation
Seek service assistance.
12
[ERROR: PHOTOSENS]
Error during photosensor
operation
Seek service assistance.
13
N/A
Not used
14
[ERROR: SENSOR A]
[LOW TEMP]
The temperature sensor A
has measured value below
5
o
C
The circulation water is with
dangerously low
temperature and its freezing
is possible.
Seek for service help to
check the heating
installation.
15
[ERROR: SENSOR A]
[OVERHEAT]
The temperature sensor A
has measured value over
95
o
C
Circulating water is with
dangerously high
temperatures and is
possible overheating of the
heating system and
equipment.
Seek service help to check
the heating installation.
16
[ERROR: OPTO-]
[COUPLER]
Board error
Seek service assistance.
17
[ERROR: OVER-]
[PRESSURESENS]
Not used
18
[ERROR: FAN 1]
[ALWAYS ON]
Combustion air fan can not
be stopped, possible
damage at the exit of the
controller
Seek service assistance.
19
[ERROR: FAN 1]
[STOPP]
The fan for combustion air
does not rotate
Seek service assistance.
20
[ERROR: FAN 1 RPM] []
The fan for combustion air
does not rotate at the
desired speed
Seek service assistance.
21
N/A
Not used
22
[ERROR: STOKER]
[FAULT]
Screw error
Seek service assistance.
23
[ERROR: FINAL]
[COMBUST FAILED]
Photosensor does not
shade during the final burn
out phase
Seek service assistance.