6.4.6.5 

Lock function 

If  the  locking  feature  is  enabled,  the  operation  of  a  channel  can  be  inhibited  by  writing  a  value  in  a 
communication object. 

The value written is of the KNX type “enable”; please beware that the meaning of this 

value  is  “

activate  lock

”,  which  is  not  to  be  confused  either  with  “enable 

locking  function

”  or  with  “enable 

output”. The meaning of the value can be optionally inverted through a configuration parameter (an “enable 
on” value can be interpreted as “lock off”). 

A  locked  output  ignores  the  switching  commands  that  are  received  for  the  duration  of  the  lock,  thereby 
maintaining the status it has upon lock entry. The status of the output can be set to a particular value both 
when the lock is set and when it is released; it is also possible to determine whether the lock status should 
be maintained or changed on recovery after a bus power-off. 

 

Fig. 11 - Lock function 

 

 

Содержание EK-GA1-TP

Страница 1: ...Application manual KNX 2 channel Dimmer module EK GA1 TP...

Страница 2: ...6 4 3 Output handling features 12 6 4 4 Switching feature overview 12 6 4 5 Dimming feature overview 13 6 4 6 Functional detail 15 6 4 6 1 Feedback 15 6 4 6 2 Time delay 15 6 4 6 3 Staircase function...

Страница 3: ...utput modules EK GA1 TP Release 1 5 Update 02 2022 MAEKGA1TP_EN EKINEX S p A All rights reserved Page 3 Revision Modifications Author Date 1 0 First version G Croci 15 07 2016 1 5 Added table for powe...

Страница 4: ...d reference of device features and application programming For installation mechanical and electrical details of the device please refer to the technical description datasheet Application manual and a...

Страница 5: ...ution boards For operation the devices receives KNX telegrams from the bus sent by another KNX device such as a pushbutton a sensor a display a timer etc these telegrams cause the activation or deacti...

Страница 6: ...manual and online mode LED indicators for output status and for manual mode indication terminals for input line power and output load connection terminals for KNX bus line connection Fig 1 Switching d...

Страница 7: ...during commissioning phase Product code EAN No of channels ETS application software release Communication objects max nr Group adresses max nr EK GA1 TP 8018417181214 2 APEKGA1TP knxprod 46 46 Configu...

Страница 8: ...6 Function description The device is a dimming actuator which activates its output channels according to telegrams sent by other devices on the bus It also incorporates additional features such as e g...

Страница 9: ...KNX bus is effectively inoperable 6 3 Manual operation The manual operation works as an alternative to the output switching through bus commands bus controlled mode this mode is intended for testing...

Страница 10: ...off When the LED turns on the whole membrane keypad is activated and manual operation is allowed 2 Press the pushbutton of the keypad corresponding to the desired channel and function A short press c...

Страница 11: ...be inhibited in two ways both selectable through configuration parameters by disabling the manual switching feature altogether through a bus command Please notice that the above mentioned bus command...

Страница 12: ...which for instance the effect of flags to determine how the change of value affects the transmission of the objects 6 4 3 Output handling features The outputs are dimmable AC channels each channel can...

Страница 13: ...the following scheme Fig 2 Functional blocks The above functions are mostly but not all purely digital i e related to an On Off behaviour for instance the scene management involves the definition of t...

Страница 14: ...Application manual KNX binary output modules EK GA1 TP Release 1 5 Update 02 2022 MAEKGA1TP_EN EKINEX S p A All rights reserved Page 14...

Страница 15: ...r on and or power off mode are set to soft the communication object that indicates the current position of dimming provides as feedback the actual value that will reach at the end of the ramp Similarl...

Страница 16: ...other events that allows to switch the light off before the programmed time expires e g because the person who triggered the presence sensor has surely left the building through an exit There is a pro...

Страница 17: ...ication manual KNX binary output modules EK GA1 TP Release 1 5 Update 02 2022 MAEKGA1TP_EN EKINEX S p A All rights reserved Page 17 Following pictures show the Manual Off feature Fig 4 Manual Off feat...

Страница 18: ...lication manual KNX binary output modules EK GA1 TP Release 1 5 Update 02 2022 MAEKGA1TP_EN EKINEX S p A All rights reserved Page 18 Following pictures show the Retrigger feature Fig 5 Retrigger featu...

Страница 19: ...cation manual KNX binary output modules EK GA1 TP Release 1 5 Update 02 2022 MAEKGA1TP_EN EKINEX S p A All rights reserved Page 19 Following pictures show the Pre warning feature Fig 6 Pre warning fea...

Страница 20: ...he right works as follow according to which logical operation is selected OR the output is ON whenever any one of the inputs is ON AND the output is ON only if all of the inputs are ON XOR the output...

Страница 21: ...Application manual KNX binary output modules EK GA1 TP Release 1 5 Update 02 2022 MAEKGA1TP_EN EKINEX S p A All rights reserved Page 21 Fig 8 Logic OR function Fig 9 Logic AND function...

Страница 22: ...Application manual KNX binary output modules EK GA1 TP Release 1 5 Update 02 2022 MAEKGA1TP_EN EKINEX S p A All rights reserved Page 22 Fig 10 Logic XOR function...

Страница 23: ...e confused either with enable locking function or with enable output The meaning of the value can be optionally inverted through a configuration parameter an enable on value can be interpreted as lock...

Страница 24: ...the output forcing is released and also on recovery after a bus power off if forcing was previously in effect Fig 12 Forcing function The Force command has priority over Locking which acts on the ord...

Страница 25: ...al delay can be defined for the output activation or deactivation from the moment the scene code is recalled The output value for a scene can either be fixed and chosen in the configuration phase or i...

Страница 26: ...d ad a runout alarm in case the maximum value is overflowed The power counter also has an associated KNX kWh counter communication object with its own reset command An additional parameter allows to d...

Страница 27: ...General device configuration Parameter name Conditions Settings Manual operation enabled disabled Enables the front panel pushbutton that activates manual mode Disable from bus Manual operation enabl...

Страница 28: ...el can be put in parallel with channel 1 In this case both the configuration and the values of parameters are the same there is only one set of communication objects internally associated to both chan...

Страница 29: ...switched on through a bus command Intensity when switch on Light intensity Intensity when switch on new value 1 100 slider 50 Specifies the new value for switch on Switch on type instant on soft Speci...

Страница 30: ...l be transmitted even if a switching occurs the feedback telegram for a switch during the delay period is lost Transmission cycle time Status feedback telegram enabled hh mm ss 00 00 00 Interval betwe...

Страница 31: ...r descriptions see the corresponding section below Operating energy time counter enabled disabled Enables or disables the energy time counter function For further details and parameter descriptions se...

Страница 32: ...orresponding numbers for all 8 available logic objects Output x Scene number Scene function enabled 1 Byte C W 17 001 scene number 18 001 scene control 18 40 Allows to recall a scene setting for the s...

Страница 33: ...arning feature For a detailed description see the corresponding section of this manual Pre warning Pre warning time Staircase lighting function enabled Pre warning enabled hh mm ss 00 00 10 Specifies...

Страница 34: ...how to set the lock status after bus voltage recovery Behaviour at locking Locking function enabled off on no change Defines how to set the output value when the lock is activated Behaviour at unlocki...

Страница 35: ...e device waits for the specified time before validating the logic objects used as inputs a request is sent for each logical object value which has not arrived within the read delay The maximum value i...

Страница 36: ...off on Initial output value for the selected scene This value will be possibly overwritten by a scene store command if the Learning mode option is enabled Scene n Light intensity Scenes function enabl...

Страница 37: ...to this output The total energy consumed kWh is calculated as the product of the specified value W and the operating hours h Energy time cyclic sending Operating hours energy counter enabled hh mm ss...

Страница 38: ...copy parameters from 8 bit unsigned C W 5 001 Percentage 0 100 4 26 Control point for setting the absolute dimming value Output x On off status Status feedback telegram enabled 1 bit CR T 1 001 switch...

Страница 39: ...ding to logic objects 1 to 8 are listed Output x Scene number Scene function enabled 1 Byte C W 17 001 scene number 18 001 scene control 18 40 Allows to recall a scene setting for the status of the ou...

Страница 40: ...MAEKGA1TP_EN EKINEX S p A All rights reserved Page 40 Object name Conditions Size Flags DPT CO number s Output x Hours counter runout Operating hours energy counter enabled 1 bit CR T 1 005 alarm 23 4...

Страница 41: ...defective devices must be returned to the manufacturer at the following address EKINEX S p A Via Novara 37 I 28010 Vaprio d Agogna NO Italy 7 3 Other information This application manual is aimed at in...

Отзывы: