Application manual
KNX binary output modules EK-GA1-TP
Release 1.5 - Update: 02/2022
MAEKGA1TP_EN
© EKINEX S.p.A. - All rights reserved
Page 30
Parameter name
Conditions
Settings
Behavior at bus off
-
off
on
no change
Allows to determine the state of the output when a bus voltage failure is detected.
Behavior at bus on
-
off
on
no change
previous state
Allows to determine the state of the output after bus recovery.
Behavior after download
-
off
on
no change
Allows to determine the state of the output when the device resumes operation after a new
parametrization has been downloaded.
Status feedback telegram
-
enabled
/ disabled
Enables or disables the automatic sending of a feedback telegram following an output change; this
refers to both the On/off status and an intensity variation.
Delay after bus voltage
recovery
Status feedback telegram = enabled
hh:mm:ss.fff
(
00:00:03.000
)
Time after bus voltage recovery before status feedback telegrams begin to be sent.
The delay has no effect on the behaviour of the outputs; only the feedback telegrams are delayed. The
outputs can therefore be activated during the delay after a bus voltage recovery.
During this delay, no feedback telegram will be transmitted even if a switching occurs; the feedback
telegram for a switch during the delay period is lost.
Transmission cycle time
Status feedback telegram = enabled
hh:mm:ss
(
00:00:00
)
Interval between cyclical transmissions.
A zero value (00:00:00) means no cyclical transmission (feedback telegrams are only sent on value
change).
Values less than “00:00:10” (ten seconds) are considered by the firmware in any case as 10 (ten)
seconds; the maximum value is 18:12:15.
On delay time
-
hh:mm:ss.fff
(
00:00:00.000
)
Delay between the “On” command telegram and the actual output activation.
This time delay does not affect the output of the staircase and forced control functions.
For the scene function the delay can be set separately.
Updating the object from "ON" to "ON" or from "OFF" to "OFF" retriggers the delay time.
Off delay time
-
hh:mm:ss.fff
(
00:00:00.000
)
Delay between the “Off” command telegram and the actual output deactivation.
Same comments as
for the “On delay time” parameter apply.
Staircase lighting function
-
enabled /
disabled
Enables or disables the staircase lighting feature.
For further details and parameter descriptions see the corresponding section below.
Lock function
-
enabled /
disabled
Enables or disables the capability of locking the input through a remote command.
For further details and parameter descriptions see the corresponding section below.
Forced function
-
enabled /
disabled