Application manual
KNX binary output modules EK-GA1-TP
Release 1.5 - Update: 02/2022
MAEKGA1TP_EN
© EKINEX S.p.A. - All rights reserved
Page 35
6.5.3.4
Logic function
This folder is enabled if
Channel X
Main parameters
Logic function =
enabled
.
Parameter name
Conditions
Settings
Logic operation type
Logic function = enabled
OR
AND
XOR
Defines the logic operation to perform on allowable inputs.
Read delay after bus
recovery
Logic function = enabled
hh:mm:ss.fff
(
00:00:10.000
)
After a bus voltage recovery, the device waits for the specified time before validating the logic objects
used as inputs; a request is sent for each logical object value which has not arrived within the read
delay.
The maximum value is 00:10:55.350.
Logic object
n
Logic function = enabled
disabled
/ enabled
Defines which logic object is used as input.
Disabled logic objects are completely ignored and corresponding communication objects do not
appear.
Logic object
n
–
Logic object
n
negated
Logic function = enabled
Logic object n = enabled
no
/ yes
Applies a logical negation to the value of the input object.
The logic function is carried out only if, and whenever, at least one of the enabled input objects
is updated by a bus telegram.
i