Installing the AIM module into a rack
AIM2505A Technical Manual V2.03
14
3.1.2 Preparations
Before you start installing the AIM module to a rack, make the following preparations.
Make sure you have a Pozidrive Pz0 or Pz1 screwdriver to tighten the front
panel fastening screws on the module.
Check the shipping container to see that it is not damaged.
Take the module out of its shipping container carefully. The module is always
shipped in an ESD protective wrapping.
Check the module, especially the connectors, for any visible signs of damage
that may have occurred during shipment.
Installation procedure
The following sections include instructions for installing the AIM module into a rack.
3.2.1 Installing the AIM module into the rack
1. Check that the coding pins are installed according to the project specifications
2. Hold the module by the front connector.
3. Place the module on the rails of the rack.
4. Slide the module towards the back plane of the rack until it clicks into its
place. Do not use force.
5. Tighten the two screws (Pozidriv head collar screws) on the front panel.
6. If there are other modules in the rack, make sure that the front connector of
the AIM module is at the same level with the other modules.
If the module does not fit into its place in the rack refer to section 3.4 “Potential
problems in the installation procedure” on page 17.