17 Technical Data
17.1 PCS cabinet data
Model
ACB05-PE
Electrical & performance data, AC
Grid voltage
230 / 240 Vac
Grid frequency
50 Hz
Maximum continuous operating current
21.7 Amps
Maximum continuous operating power
5000 VA
Power factor, nominal (range)
> 0.99 (0.8 lead to 0.8 lag)
Efficiency, % peak (average)
96 (94.5)
Maximum AC fault current and duration (short circuit)
248 Apk, 7.97 Arms for 0 to 50ms
Inrush current
0 Amps
Galvanic isolation
transformer
AC connections, number (type)
2 (grid, backup)
Maximum output overcurrent rating, grid & backup
63A maximum
Grid withstand short circuit capability
10kA, 1 second
PV solar coupling method
AC only (PV inverter not included)
PV power limit, AC only, backup connection
5000 VA
PCS self consumption power, sleep (operating)
6.4 W (30 W)
Backup power surge rating
170 %, 3 seconds
Lightning protection
IEEE 62.41.2, location category B, low exposure
Active anti-islanding method
Sandia frequency shift
Protective Class (I, II, or III)
Class I
Over-Voltage Category (OVC I, II, III, or IV)
OVC III
Inverter topology type
Isolated
Electrical data, DC
Nominal DC Voltage / DC Voltage range
48 V / 40 to 66 V
Maximum DC Current
Discharge = 125 A / charge = 100
Storage Type
Lithium, Lead Acid, other
General data
Width / Depth / Height
529
mm / 397 mm / 783 mm
Weight
65 kg
Installation type
Wall-mount (upright)
PV solar coupling method
AC only (PV inverter not included)
DRED device support
DRM 0, 1, 2, 4, 5, 6, 8
Ground fault monitoring
DC negative grounded
Lightning protection
IEEE 62.41.2, location category B, low exposure
Display
LED: battery SOC, grid connect state, service
Environmental data
Ingress protection rating
IP34
Pollution Degree
3
Cooling method
Fan, thermostat control
Ambient temperature, relative humidity, altitude
-40
°C to +50
°C, 95%, 2000 m
Testing to Section 5 of AS/NZS 4777.2:2020 for multiple inverter combinations has not been conducted.The PCS
AC and DC sources are galvanically isolated. As a result, there is no earth fault indication.