UPS RMH700/1000/1500
Instruction Manual
RMH Series
Page 20 of 37
8 Installing and connecting the UPS
All requirements in the technical data regarding environmental and operating
conditions must be observed to ensure trouble-free functioning of the UPS.
The following must be observed when setting up / installing the UPS
equipment:
o
Avoid extremes of temperature and atmospheric humidity. A maximum
service life, also in relation to the accumulators, is achieved at an
ambient temperature of 15 – 25°C.
o
Always ensure that sufficient space is available behind the UPS to
make the necessary connections and, as the UPS is heavy, use
suitable guide rails during installation. The load-bearing capacity of the
base must be ensured without fail.
o
Observe the specified installation location and only mount the
equipment using the screw-in positions shown (Fig. 5).
Fig. 5: Front view,
showing installation
position and
mounting points
o
Make sure that the equipment is ventilated. As this UPS is ventilated in
a crosswise and lengthwise direction, a minimum clearance of at least
50 mm between the UPS and the cabinet in which it is installed must be
maintained on the right and left sides as well as at the front and back.
Ensure an appropriate flow channel.
o
Pay attention to the arrangement of the equipment. When installed in
parent systems (e.g. machine, control cabinet), you must ensure that
the UPS operates within the specified temperature range. Sufficient
forced ventilation must be used to remove excess heat that builds up in
the space where the UPS is installed.