Connections in Detail
2-19
Port
Type
Left Hand RJ45
2
9
G,S
T
V
TB9-1
+V
+V
+V +V
TB9-2
TB9-3
TX2+ TX2+
TB9-4 GND
GND
GND
GND GND
TB9-5
RX2
RX
TB9-6 TX2-
TX2
TX
TX2-
TB9-7
RX2- RX2-
Tx2-/Rx2-
(B)
TB9-8
RX2+ RX2+
Tx2+/Rx2+(A)
•
Table 2-12 Mk10A TB9 connections
Symbol Direction
Description
+V
Output
External Modem supply: 12-20 VDC at 3.6W
GND
Output
Ground for all signals and supply
TX Output
RS232
Transmit
RX Input
RS232
Receive
DTR
Output
RS232 Data Terminal Ready
CD
Input
RS232 Carrier Detect
TX+
Output
4-wire RS485 Tr (A)
TX-
Output
4-wire RS485 Transmit - (B)
RX+
Input
4-wire RS485 R (A)
RX-
Input
4-wire RS485 Receive - (B)
Tx+/Rx+(A)
I/O
2-wire RS485 Transmit/R (A)
Tx-/Rx- (B)
I/O
2-wire RS485 Transmit/Receive - (B)
Blank
No
Connection
•
Table 2-13 Symbol Descriptions
See Figure 2-8 for the location of the RJ45 connector. It is designated as TB1.
FLAG Port
The meter can have either a Flag Port or an ANSI Port. Use a standard FLAG (IEC1107
physical standard) read head to connect the meter to a PC.
Note that it has occasionally been found that some FLAG heads need to be rotated 180
degrees for them to work. If you have problems try this.
ANSI Port
The meter can have either Flag Port of ANSI Port. Standard Flag and ANSI read heads
should work with the meter. Please note that older EDMI ANSI read heads will not
work with the meter. To use a smart read head that can automatically switch polarity,
set the DTR line to be low – see
Configure
in the
Site Properties
section of the
EziView
Basics
chapter in the Atlas Software Reference Manual.