55
9 - START UP PROCEDURE
**
See Tables : Section 12.4 -Parameters for High Altitude
9.16 Description Of Parameters: Factory Settings conti.
FACTORY SETTINGS
100,
125,165
115,
150,205
The values listed below are factory defaults, there may be differences for each application
Model
100
115
125
150
165
205
Fuel
Natural
LP
Natural
LP
Natural
LP
Natural
LP
Natural
LP
Natural
LP
P70
Ignition Fan Speed**
Setting
35
35
38
38
44
44
RPM
3500
3500
3800
3800
4400
4400
P71*
Maximum Fan Speed**
Setting
85
220
115
220
105
120
225
RPM
5850
7200
6150
7200
6050
5700
7250
P72
Minimum Fan Speed**
Setting
50
55
40
40
43
45
40
RPM
1250
1300
1150
1150
1180
1200
1150
To calculate fan speeds
(P70 x 100)
(P71 x 10) + 5000
* For 165 Model: (P71 x 10) + 4500
(P72 x 10) + 750
P73
Boiler Power Selection
1
= 115
2
= 100
3
= 150
10
= 125
11
= 205
12
= 165
Default depends on firing
rate of boiler as listed.
P74
CH mode burner ignition delay after burner off due to water temperature exceeding limit setting with an interrupted call for heat
Range
=
0-255 seconds (0-4.25 min.)
0
P78
0-10V Input
0
= Disabled
1
= Temperature Setpoint (3V = minimum setpoint, 10V = maximum setpoint
2
= Power Setpoint (3V = minimum power, 10V = maximum power)
0
P82
4
= Disabled
3
= Enabled 0-10V DC Input
4
P11..P12
Manufacturer information
--
P13
Max. heating output
(0-100%)
100
80
P14
DHW max. output
(0-100%)
100
P15
Min. heating output
(0-100%)
00
P16
Maximum CH set-point (°C)
00
= 176°F (80°C)
01
= 113°F (45°C)
Selectable Range 20-80 = (20°C to 80°C) 68°F to 176°F
00
P17
Pump overrun time in heating mode
(01-240 minutes)
03
P18
CH mode burner ignition delay after burner off due to water temperature exceeding limit setting with a continuous call for heat
03
P19
Manufacturer information
07
P20
Pump overrun time in DHW mode
(seconds)
30
P21
Anti-legionellosis function
00
= Disabled -
01
= Enabled
00
P22
Manufacturer information
(set “
22
” to display parameters
42
and above
)
00
P23
Maximum DHW set-point temperature
113°-140°F (45°-60°C), Default 49 = 120°F
49
P24
Manufacturer information
35
P25
No water safety device
00
P26..P31
Manufacturer information
--
P32..P41
Diagnostics (See SERVICE Instructions)
--
P44
Temperature unit setting
00
= °C
01
= °F
01
P67
OT/RT (Open Therm / Room Thermostat) selection.
0
= Plug and Play
1
= B&P
2
=OT (open therm STD)
02
NOTE
: To scroll to parameter
42
and above
it is necessary to set
P22
to
22
before scrolling up to the parameter.
240013354 REV A [07/01/2021]
Содержание Utica Boilers MAC-115
Страница 2: ...MAC 205...
Страница 4: ...MAH 165...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013354 REV A 07 01 2021...
Страница 78: ...74 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013354 REV A 07 01 2021...
Страница 79: ...75 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013354 REV A 07 01 2021...
Страница 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013354 REV A 07 01 2021...
Страница 81: ...77 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013354 REV A 07 01 2021...
Страница 115: ...32 CIRCULATOR CONNECTIONS WIRING DIAGRAM Single Zone Circulator Wiring Using ARGO AR822 II PN 240011430 REV O 07 01 2021...
Страница 117: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 118: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 119: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Combi PN 240011430 REV O 07 01 2021...
Страница 120: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 121: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 126: ...43 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV O 07 01 2021...
Страница 131: ...48 3 FAULT SOLUTION SECTIONS PN 240011430 REV O 07 01 2021...
Страница 134: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240011430 REV O 07 01 2021...