17
5 - COMBUSTION AIR AND VENT PIPING
WARNING
Fire, explosion, and asphyxiation hazard. Improper
installation could result in death or serious
injury. Read these instructions and understand all
requirements before beginning installation.
!
• Venting shall be supported adjacent to each joint using
steel strapping or equivalent. See Figure 5-1.
• Support horizontal sections of vent pipe to prevent sags
capable of accumulating condensate.
• Assemble vent materials in accordance with venting
manufacturer’s instructions.
• Slope exhaust pipe minimum of 1/4” per foot, or vent
manufacturer’s recommendation, whichever is greater;
back toward the boiler.
•
Any "in line" elbows in flue system must be taken into
consideration. First elbow on the top of the boiler is
included in equivalent length calculations.
• Use U.V. stabilized polypropylene when it will be exposed
to sunlight, wind, or prone to freeze ups.
• Check for proper joint construction when joining pipe to
fittings.
• Manufacturer requires use of an approved mechanical
fastener, which may vary per vent pipe manufacturer, at
every push-fit gasket connection when using a single wall
polypropylene vent system.
•
Refer to specific vent manufacturer's manual for additional
support.
WARNING
ABS/PVC venting shall not to be used this product.
Use of DWV plumbing pipes to vent this boiler shall be
prohibited.
Use of cellular core PVC (ASTM F891), cellular core
CPVC, or Radel® (polyphenol sulfone) in venting
systems shall be prohibited.
Covering non-metallic vent pipe and fittings with
thermal insulation shall be prohibited.
Failure to follow these instructions could result in death
or serious injury.
!
Note
Follow venting manufacturer's equivalent lengths
for specialty fittings.
Figure 5-1 - Venting Support
• This boiler requires a dedicated direct vent system.
• Vent connections serving appliances vented by natural draft
shall not be connected into any portion of mechanical draft
systems operating under positive pressure.
• Use only manufacturer approved venting materials or
venting materials primer and glue approved to: ULC S636
in Canada, or UL 1738 in the U.S.
• Materials used in the U.S. shall comply with Authority
having jurisdiction and in absence of such with: ANSI/ASTM
D1785, ANSI/ASTM F441, ANSI/ASTM F493.Vent system
must have unrestricted movement through walls, ceilings
and roof penetrations.
• Check for proper joint construction when joining pipe to
fittings.
•
If vent is penetrating ceilings and floors, openings must
have means of fire stopping in joist areas and proper fire-
stop spacer assemblies installed.
•
Standard roof flashing methods must be used to install roof
flashing.
• Frame wall and roof openings to provide support for
attachment of termination assemblies.
• Support piping in accordance with pipe manufacturer's
instruction and authority having jurisdiction. In absence
of manufacturer's instruction use pipe hooks, pipe straps,
brackets, or hangers of adequate and strength located
at intervals of 3 ft. (1.m) or less. Allow for expansion/
contraction of pipe.
5.1 General
• Installations shall comply with Authority having jurisdiction
and in absence of such with:
»
U.S. ANSI Z223.1 /NFPA 54 in the United States
240013354 REV A [07/01/2021]
Содержание Utica Boilers MAC-115
Страница 2: ...MAC 205...
Страница 4: ...MAH 165...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013354 REV A 07 01 2021...
Страница 78: ...74 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013354 REV A 07 01 2021...
Страница 79: ...75 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013354 REV A 07 01 2021...
Страница 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013354 REV A 07 01 2021...
Страница 81: ...77 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013354 REV A 07 01 2021...
Страница 115: ...32 CIRCULATOR CONNECTIONS WIRING DIAGRAM Single Zone Circulator Wiring Using ARGO AR822 II PN 240011430 REV O 07 01 2021...
Страница 117: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 118: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 119: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Combi PN 240011430 REV O 07 01 2021...
Страница 120: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 121: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 126: ...43 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV O 07 01 2021...
Страница 131: ...48 3 FAULT SOLUTION SECTIONS PN 240011430 REV O 07 01 2021...
Страница 134: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240011430 REV O 07 01 2021...