65
For elevations between 2000 ft (600 m) and 10,000 ft (3048 m), use the following information:
Altitude
Model
Number
Input, MBH (KW)
Heating
Capacity,
MBH*
AFUE, %
Domestic Hot Water (DHW) Circuit
**
Maximum
Minimum
Max Input,
MBH
Min Input,
MBH
Max Output,
MBH
Min Output,
MBH
2,000-4,500 ft
(600m-1350m)
MAH-100
88.8
16.5
81.1
95.0
MAC-115
88.8
16.5
81.1
95.0
109.7
16.6
100.2
15.3
MAH-125
113
22
101
95.0
MAC-150
113
22
101
95.0
137
22
122
19
MAH-165
147
26.5
137
95.0
MAC-205
147
26.5
137
95.0
184.5
26.5
157
23
4,501-6,500 ft
(1372 m -1981 m)
MAH-165
135
24.1
126
95.0
MAC-205
135
24.1
126
95.0
168
24.1
143
20
6,501-10,000 ft
(1982 m -3048 m)
MAH-165
113
20.3
105
95.0
MAC-205
113
20.3
105
95.0
141
20.3
120
17
*
Max CH Supply temp 176° F (80° C) for MAH-125 and
MAC-150
*
Max DHW temp 140° F (60° C)
**MAC
-150 Max DHW Flow rate 3.5 gpm (13.2 l/min)
**
MAC
-205 Max DHW flow rate 5.0 gpm (18.9 L/min)
12.3 High Altitude Ratings
12.4 High Altitude Chart
GAS
Natural
LP
Model
Altitude
0-2,000 ft.
[0-610 m]
2,000- 10,000 ft
[610-3,048 m]
0-2,000 ft.
[0-610 m]
2,000- 10,000 ft
[610-3,048 m]
Parameter
P71
High Fire
Fan Speed
100
Setting
RPM
85
5,350
75
5,250
85
5350
75
5250
115
Setting
RPM
220
7,200
190
6,900
220
7,200
190
6,900
125
Setting
RPM
115
6150
60
5600
65
5650
40
5400
150
Setting
RPM
220
7200
170
6700
170
6700
150
6500
165
Setting
RPM
105
6050
120
6200
205
Setting
RPM
225
7250
220
7200
Parameter
P72
Low Fire
Fan Speed
100
Setting
RPM
50
1,250
70
1450
115
Setting
RPM
55
1,300
55
1,300
125
Setting
RPM
40
1150
25
1000
150
Setting
RPM
40
1150
25
1000
165
Setting
RPM
43
1180
60
1350
45
1200
60
1350
205
Setting
RPM
40
1150
60
1350
45
1200
60
1350
CO Limit < 200 ppm
12 - RATINGS AND CAPACITIES
240013354 REV A [07/01/2021]
Above 2000 ft. (610m) boiler will derate by 4% for each 1,000 ft (305M) of altitude gain.
Содержание Utica Boilers MAC-115
Страница 2: ...MAC 205...
Страница 4: ...MAH 165...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013354 REV A 07 01 2021...
Страница 78: ...74 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013354 REV A 07 01 2021...
Страница 79: ...75 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013354 REV A 07 01 2021...
Страница 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013354 REV A 07 01 2021...
Страница 81: ...77 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013354 REV A 07 01 2021...
Страница 115: ...32 CIRCULATOR CONNECTIONS WIRING DIAGRAM Single Zone Circulator Wiring Using ARGO AR822 II PN 240011430 REV O 07 01 2021...
Страница 117: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 118: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 119: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Combi PN 240011430 REV O 07 01 2021...
Страница 120: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 121: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Страница 126: ...43 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV O 07 01 2021...
Страница 131: ...48 3 FAULT SOLUTION SECTIONS PN 240011430 REV O 07 01 2021...
Страница 134: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240011430 REV O 07 01 2021...