Water boiler piping. See Figures 2 and 3.

1. 

 

Determine where the boiler, the space heating, and the water heater connections should be made based on the 

type of piping system that is either in place, or is to be installed for a new hydronic system installation. See 

Figure 2, Boiler Water Piping with Zone Circulators, and Figure 3, Boiler Water Piping with Zone Valves.

2. 

 

It is recommended that 1” pipe and 1” zone valves be used on the water heater zone.

Zone Circulator System

For space heating systems that use Zone Circulators, refer to Figure 2. The water heater connection labeled 

“BOILER SUPPLY” should be piped to the boiler supply piping after the air purger and before the space heating 

takeoffs. Mount the water heater circulator as close as possible to the water heater, and make sure the flow 

arrow points toward the water heater. The use of shut-off valves is recommended for future service convenience.

The water heater connection labeled “BOILER RETURN” should be piped to the boiler return piping as close to 

the boiler as possible and after any flow control or check valves in the space heating return piping. The use of a 

union and a shut-off valve is recommended. The use of a check valve is required to prevent back flow through 

the water heater during operation of the space heating system.

Zone Valve System 

For a space heating system that uses Zone Valves, refer to Figure 3. The water heater connection labeled 

“BOILER SUPPLY” should be piped to the boiler supply piping after the air purger and before the space heating 

circulator. Mount the water heater circulator as close as possible to the water heater, and make sure the 

flow arrow points toward the water heater. The use of a shut-off valve is recommended for future service 

convenience.

The water heater connection labeled “BOILER RETURN” should be piped to the boiler return piping as close to 

the boiler as possible and after any flow control or check valves in the space heating return piping. The use of a 

union and a shut-off valve is recommended. The use of a check valve is required to prevent back flow through 

the water heater during operation of the space heating system.

Thermal expansion tank – Optional
Required if cold water line is equipped with a backflow preventer or pressure reducing valve.

Water hammer arrester – Optional
 

Dishwashers, clothes washers, and fast-closing positive shutoff valves incorporated in the system all 

contribute to creating water hammer. Install a water hammer arrester to prevent damage to pipes and appliances. See 

control manufacturer's instructions for application and installation.

unions
Use dielectric unions or couplings to protect hot and cold water fittings from corrosion when connecting dissimilar 

materials such as copper and galvanized pipe.

Backflow preventer – Optional 
Required for Commonwealth of Massachusetts

Vacuum breaker – Optional
Required for Commonwealth of Massachusetts

Содержание H2O60DE

Страница 1: ...I80DE H2 OI115D H2 OI115E H2 OI115DE An ISO 9001 2008 Certified Company ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com Information and specifications outlined...

Страница 2: ...is operating Do not touch any components unless they are cool Failure to follow all instructions in the proper order can cause personal injury or death Read all instructions including all those contai...

Страница 3: ...defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product Indicates a presence o...

Страница 4: ...180 H2O080E 80 8 0 56 0 28 0 1 NPT 150 145 H2O60E 60 8 3 62 3 23 5 1 NPT 150 135 Dual Coil No Electric Backup H2O115D 115 7 4 8 9 74 0 28 0 1 NPT 150 205 H2O80D 80 7 4 8 0 56 0 28 0 1 NPT 150 175 H2O...

Страница 5: ...w Pressure Drop gal hr gal hr Through Coil Through Coil Top Coil Bottom Coil gal min Ft Water 115 Gal Units 190 214 10 0 3 9 80 Gal Units 180 214 10 0 3 6 60 Gal Units 185 214 10 0 3 5 Note All Rating...

Страница 6: ...l based on the expected water usage for the given site The average residence with one shower or more will require a Model 40 or larger The Model 30 should only be considered for residences with minima...

Страница 7: ...e The water heater is controlled with an additional zone valve Select a valve with a low pressure drop and assure minimum flow with adequate pipe sizing B Priority or Non Priority for Hot Water 1 Opti...

Страница 8: ...e boiler system during service 2 Unions Allows for easy locating or removal 3 Vacuum breaker Protects the water heater from collapse if a hot tank is valved off to service other components in the syst...

Страница 9: ...the domestic water system 2 Position the water heater in the final location 3 Connect the cold water supply piping Install piping onto cold inlet connection Connect to cold water supply connection usi...

Страница 10: ...hat uses Zone Valves refer to Figure 3 The water heater connection labeled BOILER SUPPLY should be piped to the boiler supply piping after the air purger and before the space heating circulator Mount...

Страница 11: ...11 Figure 2 Typical Mixing Valve Install Figure 1 Domestic Water Piping Pipe Relief Valve Discharge to within 6 of floor see Section III Notes...

Страница 12: ...Discharge to within 6 of floor see Section III Notes Pipe Relief Valve Discharge to within 6 of floor see Section III Notes Figure 3 Boiler water piping with zone circulators Figure 4 Boiler water pip...

Страница 13: ...13 Pipe Relief Valve Discharge to within 6 of floor see Section III Notes Figure 5 Figure 6 Figure 7 Pipe Relief Valve Discharge to within 6 of floor see Section III Notes...

Страница 14: ...of hot water Hot Water Can Scald Water heated to temperature for clothes washing dish washing and other sanitizing needs can scald and cause permanent injury Children elderly and infirm or physically...

Страница 15: ...temperature in the water heater If it is set too high the resulting hot water can cause painful scalding with possible serious and permanent injury The temperature at which this occurs varies with a p...

Страница 16: ...ing our ARM 4P Panel Product features include Build in transformer that will support up to 15 zones Transformer has electronic fuse protection 1 to prevent transformer overloading Data Port Terminal f...

Страница 17: ...17 BOILER T T BOILER T T BOILER T T...

Страница 18: ...All wiring shall be done in accordance with all applicable local and state codes Adjusting Thermostat Temperature Dial Minimum potable water temperature can be changed by adjusting thermostat Before a...

Страница 19: ...roblem Symptoms are identical to sediment buildup If repeated flushing does not resolve the problem chemical cleaning may be required Contact a qualified contractor VII Troubleshooting PROBLEM CAUSE S...

Страница 20: ...0 1st HOUR CONTINUOUS GAL HR GAL HR GAL HR GAL HR GAL HR GAL HR RATING RATING Boiler flow 14 gpm Boiler flow 14 gpm RATING RATING RATING RATING 1st HOUR CONTINUOUS 1st HOUR CONTINUOUS 1st HOUR CONTINU...

Страница 21: ...21...

Страница 22: ...nth 13th year from the original date of installation seventy five percent 75 Within the fourteenth 14th year through the fifteenth 15th year from the original date of installation eighty percent 80 Pl...

Страница 23: ...ble all other terms and provisions hereof shall nevertheless remain effective and shall be enforced to the fullest extent permitted by law The warranties made under this Limited Warranty are exclusive...

Страница 24: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13504 4729 web site www ecrinternational com H2 O...

Отзывы: