5 - COMBUSTION AIR AND VENT PIPING
5.14 (3" / 80 mm Only) Flexible Vent System
Flexible Pipe Minimum & Maximum Vent Lengths
3” [80 mm]
Diameter Pipe
75/100/115/125/150
165/205
Min
Max
Min
Max
Natalini
Exhaust
6 ft
[1.8 m]
75 ft
[22.8 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
6 ft
[1.8 m]
50 ft [15.2
m]
6 ft
[1.8 m]
50 ft
[15.2 m]
DuraVent
®
Exhaust
6 ft
[1.8 m]
82 ft [24.9
m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
6 ft
[1.8 m]
50 ft [15.2
m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Centrotherm
Exhaust
6 ft
[1.8 m]
52 ft [15.8
m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
6 ft
[1.8 m]
50 ft [15.2
m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Z-Dens
Exhaust
NA
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
Single Wall Elbows - Equivalent Length
3" [80 mm]
45° bend
0.82 ft [0.25 m]
90° bend
1.64 ft [0.50 m]
• Follow venting manufacturer's instructions on assembly
and clearances to maintain.
• Maximum vent lengths based on equivalent straight
runs only. Include rigid pipe and fittings in overall
equivalent length calculations.
• Flexible venting installations use single wall
polypropylene to pass flue gasses to base of chimney,
then flexible venting to get them to termination at the
top.
• Combustion air is not supplied through masonry
chimney. Combustion air must be from outside using 3"
[80 mm] single wall polypropylene.
• Position boiler to use minimum of rigid single wall
polypropylene venting to the chimney.
•
Avoid sharp bends in flexible venting.
FIGURE 5-33 - (3" / 80 mm Only) Flexible Venting
System CAN BE USED ON ALL SIZES
Combustion
Air
Vent Terminal
Flexible Vent
Rigid Vent
Note
Flexible vent systems shall only be run vertical.
Horizontal runs before adapting to flexible must
be rigid pipe.
Use Venting
Manufacturer
supplied base
support, not a
Tee
240013501 REV A [03/15/2022]
Содержание Dunkirk DCB-100
Страница 2: ...DCC 205...
Страница 4: ...DCB 165...
Страница 79: ...75 A 2 MODEL 75 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013501 REV A 03 15 2022...
Страница 80: ...76 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013501 REV A 03 15 2022...
Страница 81: ...77 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013501 REV A 03 15 2022...
Страница 82: ...78 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013501 REV A 03 15 2022...
Страница 83: ...79 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013501 REV A 03 15 2022...
Страница 84: ...80 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013501 REV A 03 15 2022...
Страница 85: ...81 NOTES 240013501 REV A 03 15 2022...
Страница 86: ...82 NOTES 240013501 REV A 03 15 2022...
Страница 120: ...32 PN 240011430 REV Q 03 15 2022 CIRCULATOR CONNECTIONS WIRING DIAGRAM SINGLE ZONE CIRCULATOR WIRING USING ARGO AR822 II...
Страница 121: ...33 PN 240011430 REV Q 03 15 2022 75 100 HEAT ONLY WIRING DIAGRAM MODEL 75 100 HEAT ONLY...
Страница 122: ...34 PN 240011430 REV Q 03 15 2022 MODEL 125 HEAT ONLY 125 HEAT ONLY WIRING DIAGRAM...
Страница 123: ...35 PN 240011430 REV Q 03 15 2022 MODEL 165 HEAT ONLY 165 HEAT ONLY WIRING DIAGRAM...
Страница 124: ...36 PN 240011430 REV Q 03 15 2022 115 COMBI WIRING DIAGRAM MODEL 115 COMBI...
Страница 125: ...37 PN 240011430 REV Q 03 15 2022 MODEL 150 COMBI 150 COMBI WIRING DIAGRAM...
Страница 126: ...38 PN 240011430 REV Q 03 15 2022 MODEL 205 COMBI 205 COMBI WIRING DIAGRAM...
Страница 132: ...44 PN 240011430 REV Q 03 15 2022 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES...
Страница 137: ...49 PN 240011430 REV Q 03 15 2022 3 FAULT SOLUTION SECTIONS...