5 - COMBUSTION AIR AND VENT PIPING
Twin Pipe Maximum Vent Lengths
(Includes first elbow and termination)
Boiler
75/100/115/125/150
165/205
All
Vent Size
3"
[80 mm]
2"
[60 mm]
3"
[80 mm]
2"
[60 mm]
All
Maximum
Minimum
Intake
Vent
L1
49 ft
[15m]
85 ft [25.9m]
100 ft
[30.5m]
85 ft
[25.9m]
6 ft
[1.8 m]
Exhaust
Vent
L2
147 ft
[45m]
Combined
Vent
L1+L2
196 ft
[60m]
170 ft
[51.8m]
200 ft
[60.9m]
170 ft
[51.8m]
12 ft.
[3.6 m]
5.8 Twin Pipe Systems
Twin pipe venting allows exhaust pipe and intake flue to be
separated from each other. Fresh air is drawn in at a different
area from flue terminal location.
Fig 5-8: Horizontal termination required for exhaust pipe,
fresh air inlet can use horizontal termination or raw end of
straight section of pipe.
PVC can be used on
intake
only
on twin pipe applications.
A.
Twin Pipe CPVC System
CPVC is approved for boiler exhaust. CPVC or PVC are both
approved for air intake.
To transition from Coaxial at the top of the boiler to Twin Pipe
CPVC/PVC a kit is available. See Figure 5-14 .
B.
Twin Pipe Polypropylene System
Single wall polypropylene is used for both exhaust and air
intake piping. PVC can be used on
intake only
on twin pipe
applications.
Use the appropriate transition kit to change from
prolypropylene to PVC. To transition from Coaxial, at the top of
the boiler to Twin Pipe polypropylene venting an adapter kit is
available. See Figure 5-13.
C.
Twin Pipe Separated Flue
Exhaust and combustion air intake are not located in same
general location.
See Figures 5-8, 5-9, 5-10, 5-21, 5-22.
D.
Twin Pipe - Common Atmospheric Zone
Termination
Exhaust and combustion air intake are located in same general
location and are of equal length.
See Figures 5-23
through 5-32.
Grade, Snow
& Ice
Maintain 12"(305 mm) US, 18"(457
mm) Canada clearance above highest
anticipated snow level, 24" (610 mm)
above roof.
Avoid locations where snow may drift
and block vent and combustion air.
Ice or snow may cause boiler to shut
down if vent or combustion air becomes
obstructed.
WARNING
Asphyxiation hazard! Improper installation could
result in death or serious injury. Read Twin Pipe
Installation Instructions completely and understand all
requirements before beginning installation.
!
FIGURE 5-8 - 2"/60 mm & 3"/80 mm Twin Pipe
Separated Horizontal Flue Termination
FIGURE 5-9 - 2"/60 mm & 3"/80 mm Twin Pipe
Separated Horizontal Flue Termination
FIGURE 5-10 - 2"/60 mm & 3"/80 mm Twin Pipe
Separated Horizontal Flue Termination With Tee On
Exhaust - CAN BE USED ON ALL SIZES
This Termination
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
This Termination
can be used on:
2" / 60 mm
ON ALL SIZES
3" / 80 mm
ON ALL SIZES
vent only
This Termination
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
Single Wall Elbows - Equivalent Length
3" (80 mm)
2" (60 mm)
45° bend
0.82 ft [0.25 m]
3 ft [0.91 m]
90° bend
1.64 ft [0.50 m]
5 ft [1.5 m]
NOTE: Two pipe can be installed horizontally or vertically.
240013501 REV A [03/15/2022]
Содержание Dunkirk DCB-100
Страница 2: ...DCC 205...
Страница 4: ...DCB 165...
Страница 79: ...75 A 2 MODEL 75 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013501 REV A 03 15 2022...
Страница 80: ...76 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013501 REV A 03 15 2022...
Страница 81: ...77 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013501 REV A 03 15 2022...
Страница 82: ...78 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013501 REV A 03 15 2022...
Страница 83: ...79 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013501 REV A 03 15 2022...
Страница 84: ...80 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013501 REV A 03 15 2022...
Страница 85: ...81 NOTES 240013501 REV A 03 15 2022...
Страница 86: ...82 NOTES 240013501 REV A 03 15 2022...
Страница 120: ...32 PN 240011430 REV Q 03 15 2022 CIRCULATOR CONNECTIONS WIRING DIAGRAM SINGLE ZONE CIRCULATOR WIRING USING ARGO AR822 II...
Страница 121: ...33 PN 240011430 REV Q 03 15 2022 75 100 HEAT ONLY WIRING DIAGRAM MODEL 75 100 HEAT ONLY...
Страница 122: ...34 PN 240011430 REV Q 03 15 2022 MODEL 125 HEAT ONLY 125 HEAT ONLY WIRING DIAGRAM...
Страница 123: ...35 PN 240011430 REV Q 03 15 2022 MODEL 165 HEAT ONLY 165 HEAT ONLY WIRING DIAGRAM...
Страница 124: ...36 PN 240011430 REV Q 03 15 2022 115 COMBI WIRING DIAGRAM MODEL 115 COMBI...
Страница 125: ...37 PN 240011430 REV Q 03 15 2022 MODEL 150 COMBI 150 COMBI WIRING DIAGRAM...
Страница 126: ...38 PN 240011430 REV Q 03 15 2022 MODEL 205 COMBI 205 COMBI WIRING DIAGRAM...
Страница 132: ...44 PN 240011430 REV Q 03 15 2022 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES...
Страница 137: ...49 PN 240011430 REV Q 03 15 2022 3 FAULT SOLUTION SECTIONS...