11.5 Inputs
“START PRE-METERING”.
Potential-free make contact (wiping contact with t
on
< t
pre-metering)
(with preset pre-metering delay time: wiping contact with t
on
> t
pre-metering delay time)
Contact load from LMI02: 24 V DC, 20 mA
“METERING ENABLE”:
Potential-free make contact, contact load from LMI02: 24 V DC, 20 mA
Empty message input “NIVEAU”:
Empty status monitoring for product storage container by means of reed contact or level
electrodes. Treshold limit: 500
Ω
... 1 k
Ω
11.6 Power
supply
Supply voltage (depends on instrument version)
Item no. 187601
230 V AC + 6 % - 10 %
Item no. 187602
115 V AC +/- 10 %
Item no. 187603
24 V AC +/- 10 %
Mains frequency:
50 Hz -60 Hz
Max. pre fusing:
4 A
Internal fuse protection:
Fine wire fuse 5 x 20 mm
63 mA T (for 230 V)
125 mA T (for 115 V)
630 mA T (for 24 V)
Power input:
Max. 10 W
Influence of supply voltage
on conductivity
measurement:
≤
2.5 % within permitted range
11.7 Ambient
conditions
Permitted ambient
temperature:
0 ... 50 °C
Operating range:
0 ... 65°C
Influence of ambient
temperature:
≤
1 %/10 K in the permitted range
11.8 Interference
immunity
In accordance with EN 61000-6-2
11.9
Interference emission
In accordance with 61000-6-3
Содержание LMI 02
Страница 47: ...417102012_LMI02 doc 47 Rev 9 07 08 13 Anhang 13 1 Anwendungsbeispiele Abb 13 1 Abb 13 2...
Страница 51: ...417102012_LMI02 doc 51 Rev 9 07 08 13 3 Programmier bersicht 13 3 1 AS Mode...
Страница 52: ...417102012_LMI02 doc 52 Rev 9 07 08 13 3 2 CIP Mode...
Страница 53: ...417102012_LMI02 doc 53 Rev 9 07 08 14 Konformit tserkl rung...
Страница 93: ...417102012_LMI02 doc 93 Rev 9 07 08 13 Appendix 13 1 Application examples fig 13 1 fig 13 2...
Страница 97: ...417102012_LMI02 doc 97 Rev 9 07 08 13 3 Programming overview 13 3 1 AS Mode...
Страница 98: ...417102012_LMI02 doc 98 Rev 9 07 08 13 3 2 CIP Mode...
Страница 99: ...417102012_LMI02 doc 99 Rev 9 07 08 14 Declaration of Conformity...
Страница 139: ...417102012_LMI02 doc 139 Rev 9 07 08 13 Annexe 13 1 Exemples d application Fig 13 1 Fig 13 2...
Страница 143: ...417102012_LMI02 doc 143 Rev 9 07 08 13 3 Tableau de programmation 13 3 1 AS Mode...
Страница 144: ...417102012_LMI02 doc 144 Rev 9 07 08 13 3 2 CIP Mode...
Страница 145: ...417102012_LMI02 doc 145 Rev 9 07 08 14 D claration de conformit...