417102012_LMI02.doc
- 78 -
Rev. 9-07.08
7.3.4.2 Alarm message on exceeding metering time (t
max.
function)
If the detergent concentration is significantly less than the preset rated value so that the
metering pump runs continuously, an alarm delay time is started at the same time. An
alarm message is generated if the desired concentration is not achieved in the time set for
it (t
max
). It is possible to prevent the alarm from being generated for short-term, insignificant
drops in the concentration by setting an alarm delay time (DETERGENT DELAY TIME - set
to 0180 sec in the factory).
The metering is stopped (by relay output SP1) when the set time (t
max
) expires, the alarm
message „NO DETERGENT/ CHECK METERING“ appears on the display and the external
alarm message output is activated.
Confirm the alarm message by pressing any key.
The alarm delay time must be set as follows:
1. Activate the ALARM CONTROL SETUP menu.
2. Press the
↵
key.
3. Scroll with NEXT key until the next menu is displayed.
4. Starting with the currently blinking digit, enter the required value with the or
key.
The next digit can be selected with the
↵
key.
The time can be set to a value between 10 and 9999 sec at intervals of 1 sec.
5. Press the NEXT key to confirm.
7.3.4.3 Setting the manual metering time
The SP1 output can be activated in “OUTPUT SP1 T =120 s” in the SERVICE
FUNCTIONS menu. The switch-on time is limited by the MANUAL DOSING TIME selected
(set to 0120 s in the factory).
The manual metering time must be set as follows:
1. Activate the ALARM CONTROL SETUP menu.
2. Press the
↵
key.
3. Scroll with the NEXT key until the next menu is displayed.
4. Starting with the currently blinking digit, enter the required value with the or
key.
The next digit can be selected with the
↵
key.
The time can be set to a value between 1 and 9999 sec at intervals of 1 sec.
5. Press the NEXT key to confirm.
Содержание LMI 02
Страница 47: ...417102012_LMI02 doc 47 Rev 9 07 08 13 Anhang 13 1 Anwendungsbeispiele Abb 13 1 Abb 13 2...
Страница 51: ...417102012_LMI02 doc 51 Rev 9 07 08 13 3 Programmier bersicht 13 3 1 AS Mode...
Страница 52: ...417102012_LMI02 doc 52 Rev 9 07 08 13 3 2 CIP Mode...
Страница 53: ...417102012_LMI02 doc 53 Rev 9 07 08 14 Konformit tserkl rung...
Страница 93: ...417102012_LMI02 doc 93 Rev 9 07 08 13 Appendix 13 1 Application examples fig 13 1 fig 13 2...
Страница 97: ...417102012_LMI02 doc 97 Rev 9 07 08 13 3 Programming overview 13 3 1 AS Mode...
Страница 98: ...417102012_LMI02 doc 98 Rev 9 07 08 13 3 2 CIP Mode...
Страница 99: ...417102012_LMI02 doc 99 Rev 9 07 08 14 Declaration of Conformity...
Страница 139: ...417102012_LMI02 doc 139 Rev 9 07 08 13 Annexe 13 1 Exemples d application Fig 13 1 Fig 13 2...
Страница 143: ...417102012_LMI02 doc 143 Rev 9 07 08 13 3 Tableau de programmation 13 3 1 AS Mode...
Страница 144: ...417102012_LMI02 doc 144 Rev 9 07 08 13 3 2 CIP Mode...
Страница 145: ...417102012_LMI02 doc 145 Rev 9 07 08 14 D claration de conformit...