E93.1801EN171 HWB installation manual
62
12
ELECTRICAL INSTALLATION
General
•
For operation, the water heater needs a power supply of 120 VAC/ 60Hz.
•
The water heater main supply connection is polarity sensitive.
•
The wiring for the connections can be entered at the bottom of the water heater through the wiring knock-
outs.
•
NOTICE: Before starting to work on the water heater, it must be switched off and the power supply to the
water heater must be disconnected.
•
Electrical wiring should be installed according to all applicable standards and regulations.
In the USA, electrical installation must comply with NFPA 70, National Electrical Code – latest edition,
and with any other national, state, provincial or local codes and regulations.
In Canada, electrical installation must comply with CSA C22.1, Canadian Electrical Code part 1 – latest
edition, and with any other state or local codes and regulations.
•
Wiring the water heater should only be done by a qualified
installer or licensed electrician where required
that is skilled in working on electrical installations and according to all applicable standards.
•
It is not allowed to change the internal wiring fitted by the manufacturer.
•
A spare fuse is mounted on the casing of the burner controller.
Connection mains supply
•
It is advised to use a flexible cable between the cabinet entry (at the bottom) and the connection terminal.
•
The earth wire has to be longer than the phase and neutral wire.
•
The power supply cable must be secured by tightening the cable gland at the bottom of the water heater
casing.
•
In case of a flexible cable: use crimp ferrules on each wire end for the terminal connections.
•
On the high voltage terminal, connect to numbers: 8 = Line; 9 = Neutral; PE = Earth.
Electrical connections
High power ignitor
A separate connector for an external igniter is located on the cable tree, near the
water heater controller and labelled "High power ignitor".
The "external ignition transformer" can be ordered, see § 5.1 "Accessories".
This accessory is provided with detailed mounting instructions.
LOW VOLTAGE CONNECTIONS
HIGH VOLTAGE CONNECTIONS
Содержание HWB-299
Страница 2: ......
Страница 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Страница 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Страница 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Страница 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Страница 67: ...E93 1801EN171 HWB installation manual 67...
Страница 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Страница 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Страница 123: ......