E93.1801EN171 HWB installation manual
51
Wall (Horizontal) direct venting.
10.11.1
V
ENT
/
AIR TERMINATION
-
WALL
Follow instructions below when determining vent location to avoid possibility of severe personal
injury, death, or substantial property damage.
A gas vent extending through an exterior wall shall not terminate adjacent to a wall or below
building extensions such as eaves, parapets, balconies, or decks.
Failure to comply could result in severe personal injury, death, or substantial property damage.
Maintain 12” of clearance above the highest anticipated snow level or grade or, whichever is
greater. Please refer to your local codes for the snow level in your area
10.11.2
D
ETERMINE
L
OCATION
Locate the exhaust vent/air intake terminations using the following guidelines:
1. The total length of piping for exhaust vent or air intake must not exceed the limits given in the "General Venting"
section on page 34 of this manual.
2. You must consider the surroundings when terminating the exhaust vent and air intake:
a. Position the vent termination where exhaust gases will not damage nearby shrubs, plants or air condition-
ing equipment or be objectionable.
b. The flue products will form a noticeable plume as they condense in cold air. Avoid areas where the plume
could obstruct window views.
c. Prevailing winds could cause freezing of condensate and water/ice buildup where flue products impinge
on building surfaces or plants.
d. Avoid possibility of accidental contact of flue products with people or pets.
e. Do not locate the terminations where wind eddies could affect performance or cause recirculation, such
as inside building corners, near adjacent buildings or surfaces, window wells, stairwells, alcoves, court-
yards, or other recessed areas.
f. Do not terminate above any door or window. Condensate can freeze, causing ice formations.
g. Locate or guard vent to prevent condensate damage to exterior finishes.
3. When using two pipe terminations the air intake piping must terminate in a down-turned elbow as shown in
figure "Two pipe sidewall termination of air intake and exhaust vent". This arrangement avoids recirculation of
flue products into the combustion air stream.
4. The exhaust piping must terminate horizontally in a section of straight pipe or an elbow pointed outward or
away from the air inlet, as shown in figures "Two pipe sidewall termination of air intake and exhaust vent".
Do not exceed the maximum lengths of the outside vent piping stated in this manual.
Excessive length exposed to the outside could cause freezing of condensate in the vent pipe,
resulting in potential water heater shutdown and possible blocked flue.
PVC/CPVC or PP is acceptable air intake pipe material
5. Maintain clearances as stated in this manual. Also maintain the following:
WARNING
CAUTION
WARNING
NOTICE
Содержание HWB-299
Страница 2: ......
Страница 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Страница 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Страница 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Страница 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Страница 67: ...E93 1801EN171 HWB installation manual 67...
Страница 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Страница 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Страница 123: ......