E93.1801EN171 HWB installation manual
83
4.2 Boiler settings
min.
max. Default
unit
Access
level
Description:
4.2.1 Boiler Parameters
installer
Enter the Boiler Parameters
menu
4.2.2 Module Cascade
Settings
installer
Enter the Module Cascade Set-
tings menu
4.2.3 Boiler Cascade
Settings
installer
Enter the Boiler Cascade Set-
tings menu
4.2.1 Boiler parameters
min.
max.
Default
unit
Access
level
Description:
Dis-
play
no:
CH mode
0
5
0
#
Installer
Set the CH mode
1
CH Setpoint
68
(20)
194
(90)
176
(80)
°F
(°C)
Installer
Set the CH setpoint
3
Calc. Setp. Offset
-18
(-10)
18
(10)
0
(0)
°F
(°C)
Installer
Set the offset for CH mode 1
/ 2 calculated setpoint
185
Boiler Pump Overrun
0
900
20
sec.
Installer
Set the post-circulation time
for the boiler/CH pump
5
CH Hysteresis Up
4
(2)
72
(40)
20
(3)
°F
(°C)
Installer
Set the CH hysteresis up
7
CH Hysteresis Down
4
(2)
36
(20)
9
(5)
°F
(°C)
Installer
Set the CH hysteresis down
112
Anti-Cycle Period
10
900
10
sec.
Installer
Set the burner anti-cycling
period
9
Anti-Cycle Temp. Diff.
0
(0)
36
(20)
29
(16)
°F
(°C)
Installer
Set the burner anti-cycling
differentia
10
Design Supply Temp.
39
(4)
194
(90)
185
(85)
°F
(°C)
Installer
Set CH setpoint when out-
door temperature equals
Des. Outd. T.
19
Design Outdoor Temp.
-13
(-25)
77
(25)
23
(-5)
°F
(°C)
Installer
Set the outdoor temperature
at which CH setpoint is set to
Des. Supply T.
20
Baseline Supply Temp
39
(4)
194
(90)
104
(40)
°F
(°C)
Installer
Set CH setpoint when out-
door temperature equals
Bas. Outd. T.
21
Baseline Outdoor Temp
32
(0)
86
(30)
68
(20)
°F
(°C)
Installer
Set the outdoor temperature
at which CH setpoint is set to
Bas. Supply T.
22
Design Supply Min. Limit
39
(4)
180
(82)
68
(20)
°F
(°C)
Installer
Set the outdoor reset curve
minimum setpoint
23
Design Supply Max. Limit
27
(81)
194
(90)
194
(90)
°F
(°C)
Installer
Set the outdoor reset curve
maximum setpoint
24
Warm Weather Shutdn
32
(0)
95
(35)
72
(22)
°F
(°C)
Installer
Set outdoor temperature
above which CH demand is
blocked
25
Boost Temp Increment
0
(0)
54
(30)
0
(0)
°F
(°C)
Installer
Set the setpoint boost func-
tion temperature increment
26
Boost Time Delay
0
120
20
min.
Installer
Set the setpoint boost func-
tion delay time
27
Night Setback Temp.
0
(0)
54
(30)
7
(4)
°F
(°C)
Installer
Set the CH setpoint night
setback temperature
28
DHW Mode
0
8
0
#
Installer
Set the DHW mode
35
DHW Tank Hyst. Down
0
(0)
18
(10)
9
(5)
°F
(°C)
Installer
Set the DHW tank hysteresis
down
36
Содержание HWB-299
Страница 2: ......
Страница 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Страница 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Страница 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Страница 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Страница 67: ...E93 1801EN171 HWB installation manual 67...
Страница 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Страница 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Страница 123: ......