13
6.0
Reading from the NH
3
CAN Module (SDO Read)
During configuration it may be necessary to read certain locations in the Object Dictionary (OD).
The format for a Service Data Object Read (SDO Read) is as follows:
SDO Read Tx
CAN id
byte 0
byte 1
byte 2
byte 3
byte 4
byte 5
byte 6
byte 7
0x600+NID
0x40
OD lo OD hi
Sub
OD lo = low byte of OD address
OD hi = hi byte of OD address
Sub = Subindex of OD address
A SDO Read will generate the following reply:
SDO Read Rx
CAN id
byte 0
byte 1
byte 2
byte 3
byte 4
byte 5
byte 6
byte 7
0x580+NID
Size
OD lo OD hi
Sub
Data0
Data1
Data2
Data3
Size = 0x4F (1 byte response)
0x4B (2 byte response)
0x43 (4 byte response)
OD lo = low byte of OD address
OD hi = hi byte of OD address
Sub = Subindex of OD address
Data0 always contains the Least Significant Byte (LSB) of the data present at the OD address.
Example: Read OD address 0x5008 subindex 0x32 in the module with NID = 0x10
SDO Write Tx
CAN id
byte 0
byte 1
byte 2
byte 3
byte 4
byte 5
byte 6
byte 7
0x610
0x40
0x08
0x50
0x32
The module will reply as follows:
SDO Write Rx
CAN id
byte 0
byte 1
byte 2
byte 3
byte 4
byte 5
byte 6
byte 7
0x590
0x4B
0x08
0x50
0x32
0xBC
0x02
OD address 0x5008, subindex 0x32 of the module with NID = 0x10 contains the 2 byte value
0x2BC