![Eclipse EC-P8 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/eclipse/ec-p8/ec-p8_installation-manual_4021851011.webp)
P0031-LI-02.01
11
Single EOL - N/C
This wiring configuration should be used when connecting
detection devices that only have a normally closed alarm output.
Connect the detector as shown below and ensure that the zone is
programmed for “Single EOL – N/C” operation, see page 19.
Zy
Zx Com
3K3
3K3
1 Detector
2 Detectors
Alarm
Alarm
Alarm
Double EOL
This wiring configuration should be used when connecting
detection devices that have a normally closed alarm and tamper
output. Connect the detector as shown below and ensure that the
zone is programmed for “Double EOL” operation, see page 19.
Zy
Zx Com
1 Detector
2 Detectors
Alarm
Tamper
E.O.L
Alarm
Tamper
Alarm
Tamper
E.O.L
4K7
2K2
4K7
4K7
2K2
Triple EOL
This wiring configuration should be used when connecting
detection devices that support triple EOL configuration, this will
allow the system to monitor alarm, tamper fault and mask.
Connect the detector as shown below and ensure that the zone is
programmed for “Triple EOL” operation, see page 19.
Zy
Zx Com
1 Detector
Fault
Alarm
E.O.L
2K2
2K2
4K7
Tamper
Loudspeaker Connections
The EC-P8 has a loudspeaker output capable of driving one 16
Ω
or two 8
Ω
wired in series as shown below:
16 Loudspeaker
Ω
8 Loudspeaker
Ω
8 Loudspeaker
Ω
12V
4
3
2
1
12V
4
3
2
1
The volume level can be programmed, please refer to page 24 for
details. The loudspeaker can also be tested, please refer to page
24 for further details.
Содержание EC-P8
Страница 1: ...EC P8 8 18 Zone Intruder Alarm System Installation Manual...
Страница 4: ...4 P0031 LI 02 01 1 System Overview System Configuration...
Страница 45: ...P0031 LI 02 01 45 Notes...
Страница 46: ...46 P0031 LI 02 01 Notes...
Страница 47: ...P0031 LI 02 01 47 Notes...
Страница 48: ...Technical Support Email support zetaalarmsystems com...