![background image](http://html1.mh-extra.com/html/eclipse-combustion/vortometric-v2-00/vortometric-v2-00_installation-manual_533959048.webp)
Eclipse Vortometric Burner v2.00, Installation Guide 248, 6/00
Table A.6
Atomizing Steam Press. Drop vs. Steam Flow
• Atomizing steam must be dry and superheated a minimum of 20
°
F above
saturated at the atomizer inlet.
10
60
40
20
10
80 100
4,000
200
400
600
1,000
2,000
20
30
15
40
50
60
Atomizing Steam Flow (lb/hr)
Atomizing Steam
Pressure Drop (psig)
8V
6V
10V
14V
18V
24V
32V
12V
16V
22V
28V
36V
R
ECOMMENDED
SPARE
PARTS
To make sure that the downtime of the system is as short as possible
in case of a failure, you should keep a stock of spare parts.
Recommended spare parts
PART NAME
QTY.
PART NO.
Pilot assembly
1
1
Spark rod assembly
1
1
Oil gun assembly
1
1
U.V. scanner (if used)
2
2
1-1/4" N.P.T. peepsight glass
2
13046
1-1/4" N.P.T. peepsight gasket
2
13047
1
Part number varies depending on burner size used.
2
Part number varies depending on U.V. scanner used.
A-5