For Gas Burners
1. Drive combustion air and gas valves to low fire position.
2. Shut off main gas supply valves and pilot.
3. Leave combustion air at low fire until combustion chamber and
block are cooled; once cooled, shut off combustion air fan.
4. Shut off all manual valves as required.
For Oil Burners
1. Drive combustion air and fuel valves to low fire position; shut
down the oil supply.
2. Turn on the pilot.
3. Purge the oil nozzle with the atomizing medium through the
bypass connection valves.
4. When the oil nozzle is clear of oil, then turn off the pilot.
5. Leave combustion air and atomizing medium on until the
combustion chamber and block are cooled; once cooled, shut off
the combustion air and atomizing medium supplies.
6. Shut off all manual valves as required.