Appendix
F
LOW
AND
INPUT
CHARTS
Table A.1
Combustion Air Pressure Drop vs. Burner Heat
Input for Medium Intensity Burners (MI)
0.1
6V
8V
10V 12V 14V 16V
22V
28V
18V
24V
32V 36V
0.6 0.8 1
2
4
6
8 10
20
40
60
80 100
200
300
0.2
0.4
0.6
0.8
1
2
3
4
5
6
7.5
Burner Gross Heat Input (MMBtu/hr.)
Combustion Air Pressure Drop ("w.c.)*
* 7.5"w.c. is the nominal design pressure drop for all models,
except for model 6V of the medium intensity burners.
•
(14.7 psia @ 70
°
F).
• Pressure drop should be taken between the chamber and windbox pressure tap.
A-1
Operation with 15% excess air on natural gas under standard conditions
Eclipse Vortometric Burner v2.00, Installation Guide 248, 4/10/07