NPT-1020 Installation and Maintenance Manual
Installing Equipment
ECI Telecom Ltd. Proprietary
4-47
Figure
4-43: PME1_63 traffic cable installation
To route the PME1_63 traffic cable:
1.
Bend the cables from the connector installed in the previous procedure towards the cable guide and
holder unit (see the preceding figure).
2.
Insert a Velcro strip into the corresponding holes in the cable guide, route the cables through the strip
and tighten the strip on the cables.
3.
Place the cable conversion box on the NPT platform.
4.
Route the 26AWG cables coming from the conversion box to the rack side rails and tighten them to
the rails with cable ties.
5.
Use a cabling diagram of the site to associate the PME1_63 with the appropriate DDF connections.
4.9.4.6
Routing and Connecting Coaxial Cables
Individual coaxial cables are used for connecting the interfaces located on the electrical STM-1 SFPs on the
XIO30_1 and the xDDF-21.
As part of the site preparations, suitable cables must be routed from the relevant DDF (if used) to the
intended rack location and connected to DIN 1.0/2.3 connectors. Cable length must be sufficient to routine
the cables to the appropriate level in the rack.