Power Transformer Selection
Select a 24 VAC transformer based on the maximum power requirements indicated on the transmitter label (20 VA) or
from the table below. The operating supply voltage (transmitter power “ON” with all sensor probes connected) should
not be less than 22.8 VAC or greater than 26.4 VAC.
Connecting Power to the Transmitter
Slide the cover plate up and off of the transmitter enclosure, and ensure that the power switch is in the “OFF” position
before connecting the 24 VAC power source.
Connect 24 VAC power to the large, two position power input terminal labeled “POWER” on the upper right hand side of
the main circuit board (Figure 5). Since the output signals are isolated from the power supply, it is not necessary to pro-
vide an isolated (secondary not grounded) power source.
Multiple GTx116 transmitters wired to a single transformer must be wired “in-phase” (L1 to L1, L2 to L2).
Table 2. GTx116 Power Transformer Selection Guide
Figure 5. GTx116 Power Connections
REPLACE WITH
1.5 AMP
FAST ACTING ONLY
OUTPUT
1 2 COM
POWER
24VAC IN
L2 L1
ON
OFF
L2
L1
24 VAC
22.8 to 26.4 VAC
20 VA max
.
Power
Switch
Power Fuse
Replace with UL
®
listed, 1.5 amp, fast acting only
P.N. 800-1115 (10 pack)
LISTED
Total
Sensors
Minimum
VA Req.
Total
Sensors
Minimum
VA Req.
Total
Sensors
Minimum
VA Req.
Total
Sensors
Minimum
VA Req.
1
12
5
14
9
17
13
19
2
13
6
15
10
17
14
19
3
13
7
15
11
18
15
20
4
14
8
16
12
18
16
20