a measurable difference!
®
FROM PART 1
FROM PART 4
Dashed lines indicate Menus when # OF FLOWS=2
TO PART 6
GTC, GTM models only
GTC, GTM models only
RESET TRBL
Ĺ
ARE YOU SURE?
RESET TRBL=YES
Ļ
RESET TRBL=NO
Ĺ
TOOLS
ĹĻ
"Wait. . . %" indicates progress while the Field Adjustment Wizard acquires a large number of
samples of airflow rate and averages all of the readings. Display indicates "ADJUSTMENT
COMPLETE" when adjustment is complete.
If you wish to review the adjustment made, simply navigate back to the SETUP menu and view
the ADJUSTMENTS section.
5A
O
RESET NET
Ĺ
ARE YOU SURE?
Clears all disabled trouble settings.
RESET ADJ
ĹĻ
LOCK SEC=MED
ĹĻ
RESET ADJ=NO
Ĺ
RESET ALL=NO
Ĺ
Sets security level to MED. In this mode, a user defined code is specified. In the event of loss
of code, contact EBTRON for a unique code for this transmitter to unlock and reset code.
RESET NET=NO
Ĺ
RESET SENS
ĹĻ
ARE YOU SURE?
RESET SENS=YES
Ļ
RESET SENS=NO
Ĺ
*LOCK=OFF
Ĺ
SET LOCK?
LOCK=OFF
Ļ
LOCK=ON
Ĺ
ENTR CODE:0
Ĺ
CONF CODE:0
Ĺ
LOCK SET=HIGH
Ĺ
RESET ADJ=YES
Ļ
RESET
Ĺ
RESET ALL
Ļ
ARE YOU SURE?
RESET ALL=YES
Ļ
SECURITY
ĹĻ
*LOCK SEC=LOW
Ļ
SET LOCK SEC?
LOCK SEC=LOW
Ļ
FLOW2= 0
Ĺ
(Set 0 to 999999 using
the
ĹĻ
keys)
Wait. . .%
ADJUSTMENT
COMPLETE
SET FLOW2?
ENSURE THAT FAN IS
ON AND SET TO
DESIRED SPEED!
OUT2 TEST%
Ĺ
SET OUT2 TEST?
OUT2 TEST%=0
Ĺ
OUTPUT TEST
ĹĻ
FIELD ADJUST
ĹĻ
RUN FA WIZARD?
SET FAW INT
FAW INT=300
ĹĻ
ADJUSTMENTS
Ĺ
*OFF=0
Ĺ
SET OFF?
OUT1 TEST%
Ļ
SET OUT1 TEST?
OUT1 TEST%=0
Ĺ
FLOW ADJ=ON
Ĺ
*GAIN=1.000
ĹĻ
SET GAIN?
GAIN=1.000
ĹĻ
SET FLOW ADJ?
FLOW ADJ=OFF
Ļ
OFF=0
ĹĻ
# OF FLOWS=2
Ĺ
SET # OF FLOWS?
# OF FLOWS=1
Ļ
Set OUT2 to % of full scale analog output.
Start field adjust wizard and enter number of integration samples to use.
*FLOW ADJ=OFF
Ļ
SET FLOW1?
ENSURE THAT FAN IS
ON AND SET TO
DESIRED SPEED!
Wait. . .%
ADJUSTMENT
COMPLETE
The Field Adjust Wizard will now be engaged as outlined in the following steps.
The GAIN and OFF values will be updated, and FLOW ADJ=ON will be set if the wizard is
successfully completed.
5B
Enable/disable flow adjustments.
Enter gain applied to airflow reading.
Enter offset applied to airflow reading.
Set OUT1 to % of full scale analog output.
Enable/disable security lock.
Enter code and confirm code (NOTE: if LOCK SEC= HIGH, DO NOT lose code!)
Reset ALL changes back to factory defaults. Transmitter resets after completion.
Sets security level to HIGH. In this mode, a user defined code is specified. In the event of loss
of code, transmitter must be returned to EBTRON for unlock / reset.
FLOW1= 0
Ĺ
(Set 0 to 999999 using
the
ĹĻ
keys)
Sets security level to LOW. In this mode, there is no prompt for a lock code.
The last 4 digits of the board serial are used to unlock.
Resets sensor data. Transmitter resets after completion.
Resets network settings to factory default.
Reset FLOW adjustments to GAIN = 1, OFF = 0, FLOW ADJ = OFF
RESET NET=YES
Ļ
ARE YOU SURE?
TM_GTx116 Setup Menu (PART 5 OF 6)
42
EBTRON
, Inc. 1663 Hwy. 701 S., Loris SC 29569
•
Toll Free: 800.2
EBTRON
(232.8766)
•
Fax: 843.756.1838
•
Internet:
EBTRON
.com
G
OLD
S
ERIES
GT
X
116 T
RANSMITTER
a measurable difference!
®
TM_G
Tx1
1
6_R9A