ENGLISH
Following a long period of storage (or if some components are replaced), perform all the tests indicated by
the product regulations; to check operation, follow the indications in standard
UNI EN 12845.
4. RESPONSIBILITIES
The manufacturer declines all responsibility for the incorrect operation of the control unit if this is
tampered with or modified or operated in excess of its rated capabilities.
It also declines liability for any printing or transcription errors in this publication. It reserves the right to
make any modifications to its products that it considers to be necessary or useful, without, however,
changing their basic characteristics
5.
INSTALLATION
Strictly observe the electrical input values indicated on the rating plate.
Install the control unit on a dry surface in a non-oxidising, non-corrosive and vibration-free atmosphere. If
installed outdoors, protect the unit as much as possible from direct light; take all necessary precautions to keep
the external temperature within the limits of use indicated in chap. 6.
Elevated temperatures accelerate the ageing of all components and lead to more or less serious malfunctions.
Make sure the fitter installs the lines correctly.
6.
TECHNICAL DATA
6.1 TECHNICAL DATA PANELS FFJP 1,1T ↔ FFJP 7,5T
Rated power input:
400 V ±10%
Phases:
3
Frequency:
50-60 Hz
Panel model:
FFJP-1,1T
FFJP-5,5T
FFJP-7,5T
Maximum nominal operating power (kW):
0,37 -:- 1,1
1,5 -:- 5,5
7,5
Maximum nominal operating current (A):
1 -:- 5
3,2 -:- 16
16
Dimension (mm):
300x250x160
300x250x160
300x250x160
Weights: (kg):
7,5
7,5
7,5
Operating ambient temperature:
-10 +40°C
Storage ambient temperature:
-20 +50°C
Relative humidity (without condensation) :
50% at 40°C MAX (90% at 20°C )
Max. altitude: (without derating) :
1000 m (a.s.l.)
Protection degree:
IP55.
Construction:
EN 60204-1, EN 60439-1, EN 12845.
EMC standards applied: 61000-6-1, EN61000-6-3.
6.2 TECHNICAL DATA PANELS FFP 4T ↔FFP 75 TSD
Rated power input:
400V ±10%
Phases:
3
Frequency:
50-60 Hz
Panel model:
FFP 4 T
FFP 7,5 T
FFP 11 TSD
FFP 15 TSD
FFP 18,5 TSD
Maximum nominal operating power (kW):
1,5 -:- 4
5,5 -:- 7.5
11
15
15 -:- 18,5
Maximum nominal operating current (A):
3,5 -:- 10
12 -:- 16
24
38
38
Dimension (mm):
400x300x200
400x300x200
500x400x200
500x400x200
500x400x200
Weights: (kg):
12
12
15
15
15
Panel model:
FFP 25 TSD
FFP 37 TSD
FFP 55 TSD
FFP 75 TSD
Maximum nominal operating power (kW):
22 -:- 25
30 -:- 37
45 -:- 55
75
Maximum nominal operating current (A):
42
60 -:- 70
81 -:- 100
130
Dimension (mm):
700x500x200
700x500x200
700x500x200
700x500x200
Weights: (kg):
24
24
30
30
Operating ambient temperature:
-10 +40 °C
Storage ambient temperature:
-20 +50 °C
Relative humidity (without condensation) :
50% a 40°C MAX (90% a 20°C )
Max. altitude: (without derating) :
1000 m (a.s.l.)
Protection degree:
IP55.