3. Installation
3.4 Preparing the device for operation
The XV300 Touch Panel requires a rated operating voltage of 24 VDC from an AC-to-DC
converter with safe isolation (SELV/PELV).
power supply
Rated operating voltage
+ 24 VDC SELV (safety extra low voltage)/PELV (protective extra low
voltage)
Permissible voltage range
Effective: 19.2-30.0 V DC (rated operating voltage -20%/+25%)
Absolute with ripple: 18.0-31.2 V DC
Battery powered: 18.0-31.2 V DC (rated operating voltage -25%/+30%);
35 V DC for a duration of < 100 ms
Voltage dips
Ability to accommodate brief voltage dips
≦ 10 ms from rated operating voltage (24 V DC), ≦ 5 ms from under-
voltage (19.2 V DC)
Power consumption
XV-303-70-.., XV-313-70-..
max. 14.4 W
Current consumption at 24 V DC: 11.9 W for basic 2.5 W for
USB module
XV-303-10-.., XV-313-10-..
max. 18 W
Current consumption at 24 V DC: 15.5 W for basic 2.5 W for
USB module
fuse
Yes (fuse not accessible)
Potential isolation
no
Electrical current
7.0" display
10.1" display
Ie
≦ 0.6 A
≦0,75 A
I
TH
1.0 A²s
1.0 A²s
42
XV300
12/15 MN048017 EN www.eaton.eu