Sonix Vw2 Technical Manual

12

SONIX VW2 TECHNICAL MANUAL  

TM368 / A  May 2022  www.eaton.com

5.3  Beacon loop monitoring

The Vw2 unit will, if configured, regularly send a short 

pulse of power out of the output port of each beacon 

port and sense the energy coming back to the return 

port. If the return energy is not seen within the testing 

window, nominally ¼ second, then that beacon output 

port is considered to be ‘in fault’ and a fault flag is 

generated. Any fault flags are communicated to the 2Mx 

and then onto the wider PA/GA system.

ote: 

N

Setting to ‘Never’ prevents regular automatic testing but NOT 

manually initiated testing from the 2Mx central controller.

ote: 

N

Beacon test interval is reduced to 10 minutes in the event of a 

failed test on either port to enable faster fault recovery.

Key settings:

Beacon loop test interval  

10-30 minutes

Loop 1 Fault Monitoring   

Enabled

Loop 2 Fault Monitoring   

Enabled

6  Setup and Configuration

If the Vw2 unit is being supplied as a replacement in an 

existing system, it shall be shipped as fully configured 

for ease of replacement. Otherwise, the unit comes 

pre-configured with generic setup used for quality and 

functionality testing and should be reconfigured for 

appropriate use.

ote: 

N

Not all settings are covered in this manual, for full details on 

available settings please refer to SAS Product Manual.

Sonix modules – the Vw2 included – have been 

designed to be configurable via SAS application. A 

detailed description of all the configuration options 

is included in SAS Product Manual, but some of the 

options are worth mentioning here for clarity and 

completion.

6.1  Unit ID

Each Vw2 unit connected to the system must have a 

unique identifier, called a Unit ID. This can be set to any 

number between 1 and 31 (inclusive) and is used to 

identify the module to the 2Mx and SAS.

6.1.1  Ping set (Set a new Unit ID)

Ping set is generated by SAS and is used to give the 

target Vw2 a new Unit ID.

Unlike other Sonix modules, the Vw2 unit will accept 

the Ping Set command without acknowledging it to the 

user, meaning, that it does not require user’s action to 

confirm the change of Unit ID. Because of that, great 

care should be taken while setting the Unit ID for Vw2 

units – if there is more than one Vw2 unit connected in 

a chain, the other units should be disconnected from 

the Beacon Bus during Ping Set operations so that they 

do not acquire the new Unit ID number. An alternative 

solution is to connect directly to the unit on the top port 

connection, ensuring the data rate of SAS is adjusted to 

be standard speed not high speed.

ote: 

N

Use Ping Set on individually connected units only.

6.2  Rx Data Check

The Vw2 units monitor the Beacon Bus for Data flowing 

in both directions. In normal operation the final unit in 

the chain will not receive any data on its bottom port. 

This will generate an error; therefore Rx Data Check 

option should be set to Disabled for this unit to avoid 

false error notification. Please refer to SAS Product 

Manual  

for details.

Disabled

Rx Data Check

Содержание SONIX Vw2

Страница 1: ...SONIXTM Vw2 Termination Unit SonixTM Vw2 Technical Manual...

Страница 2: ...for a particular purpose or merchantability other than those Specifically set out in any existing contract between the parties Any such contract states the entire obligation of eaton The contents of t...

Страница 3: ...feedback 2Mx Sonix 2Mx Central controller Amp 350 d Sonix 350 W Power Amplifier with 100 V line output Eol1 Sonix Remote End of Line unit Eol8 Sonix Amplifier to 100 V line interface unit 8 channel SP...

Страница 4: ...9 4 5 1 Connecting Vw2 within standalone or A B systems 9 4 5 2 Connecting Vw2 within N 1 systems 9 4 6 Beacon power input connection 9 4 6 1 Automatic redundant power switchover 9 4 7 Beacon output...

Страница 5: ...L SIMPLIFIED VIEW OF VW2 UNIT 7 FIGURE 2 DC POWER CONNECTIONS 8 FIGURE 3 SINGLE VW2 BUS CONNECTIONS 9 FIGURE 4 MULTIPLE VW2 CONNECTIONS 9 FIGURE 5 VW2 BEACON POWER INPUT 9 FIGURE 6 REDUNDANT POWER SWI...

Страница 6: ...controller i e it receives data packets acts on that data and sends a response back to the 2Mx The robust and industrial design of the module ensures its protection against open and short circuit ass...

Страница 7: ...u remain safe throughout During this work you may be exposed to potentially hazardous voltages currents confined spaces and potentially hazardous industrial environments Prior to undertaking any work...

Страница 8: ...with signal or audio cables and reduce the possibility of interfer ence Warning Observe the polarity of incoming power supply cables Maximum cable section supported by the unit are Solid 4 0 mm2 Stra...

Страница 9: ...Vw2 Beacon power input Accepted beacon voltages are as follows if other voltages are required please contact your local Eaton representative 48 V dc 110 V ac 240 V ac Maximum cable section supported...

Страница 10: ...maximum allowable peak surge current is limited to 100 A by the on board relays The unit is fitted with a pair of 10 A 10 x 38 mm Mersen fuses part number S218194 Warning Only replace fuses with origi...

Страница 11: ...and contains system activity information from the 2Mx central controller and Vw2 status and activity going to the 2Mx 5 2 Basic operation Each output port can be configured to activate on any active...

Страница 12: ...nfigurable via SAS application A detailed description of all the configuration options is included in SAS Product Manual but some of the options are worth mentioning here for clarity and completion 6...

Страница 13: ...roved firmware The Sonix Vw2 units are controlled by a Microsemi ProASIC3 FPGA with instant on technology for fast and reliable operation To ensure correct operation of the unit it is supplied fully t...

Страница 14: ...ton and SONIX are registered trademarks All other trademarks are property of their respective owners Changes to the products to the information contained in this document and to prices are reserved so...

Отзывы: