SONIX VW2 TECHNICAL MANUAL  

TM368 / A  May 2022  www.eaton.com

6.3  Hardware configuration

Vw2 does not provide any jumpers nor switches on 

the unit itself, therefore there is no need for hardware 

configuration.

7  Unit customisation

Individual unit customisation is available. Please contact 

your local Eaton representative if the standard operation 

of Sonix system and/or Vw2 unit is not fulfilling the 

needs of your system.

8  Maintenance

The following maintenance program represents the 

minimum requirements for Sonix Vw2.

Warning:

 Power off the system before 

proceeding.

ote: 

N

Do not use sharp objects, water, aggressive cleaning agents or 

solvent to clean the unit.

• 

Check the unit for visible damage (scratches or 

bumps).

• 

Check unit fixing to rack – tighten loose screws.

• 

Check connections and cable integrity - replace 

damaged cables, tighten Phoenix connectors.

• 

Always replace the cover upon maintenance 

completion.

Appendix A - Programming the unit

Warning: 

Programming firmware is potentially 

damaging to the unit if not performed correctly 

by trained personnel and with Eaton tested and 

approved firmware. 

The Sonix Vw2 units are controlled by a Microsemi 

ProASIC3 FPGA, with instant-on technology for fast 

and reliable operation. To ensure correct operation of 

the unit, it is supplied fully tested and pre-programmed 

to the latest released version of Eaton Vw2 firmware 

(unless specified otherwise). Eaton recommend that 

firmware is only updated if there is a specific issue that 

is resolved in the updated firmware. 

Programming of the unit should only be performed by 

Eaton trained and approved personnel.

1. Equipment required for programming units:

• 

PC with Microsemi FlashPro 11.x software installed,

• 

Microsemi FlashPro4 or newer programmer, complete 

with connection cable (2x5 0.1’’ pitch)

• 

Eaton firmware for target unit (firmware is dedicated 

to each individual module and not interchangeable) 

2. The programming procedure:

• 

Connect power (48 V dc) to J3 connector, taking note 

of the correct polarity (power can be supplied from 

the rack or other rack-independent power supply),

• 

Connect FlashPro programmer to J5 connector, taking 

note of the notch orientation,

• 

Using FlashPro software program and verify unit with 

desired firmware file (see FlashPro documentation for 

details),

• 

Power-cycle programmed unit,

• 

Use SAS application to:

• 

Check or set the Unit ID,

• 

Check or set the unit configuration.

• 

Verify unit’s operation.

Содержание SONIX Vw2

Страница 1: ...SONIXTM Vw2 Termination Unit SonixTM Vw2 Technical Manual...

Страница 2: ...for a particular purpose or merchantability other than those Specifically set out in any existing contract between the parties Any such contract states the entire obligation of eaton The contents of t...

Страница 3: ...feedback 2Mx Sonix 2Mx Central controller Amp 350 d Sonix 350 W Power Amplifier with 100 V line output Eol1 Sonix Remote End of Line unit Eol8 Sonix Amplifier to 100 V line interface unit 8 channel SP...

Страница 4: ...9 4 5 1 Connecting Vw2 within standalone or A B systems 9 4 5 2 Connecting Vw2 within N 1 systems 9 4 6 Beacon power input connection 9 4 6 1 Automatic redundant power switchover 9 4 7 Beacon output...

Страница 5: ...L SIMPLIFIED VIEW OF VW2 UNIT 7 FIGURE 2 DC POWER CONNECTIONS 8 FIGURE 3 SINGLE VW2 BUS CONNECTIONS 9 FIGURE 4 MULTIPLE VW2 CONNECTIONS 9 FIGURE 5 VW2 BEACON POWER INPUT 9 FIGURE 6 REDUNDANT POWER SWI...

Страница 6: ...controller i e it receives data packets acts on that data and sends a response back to the 2Mx The robust and industrial design of the module ensures its protection against open and short circuit ass...

Страница 7: ...u remain safe throughout During this work you may be exposed to potentially hazardous voltages currents confined spaces and potentially hazardous industrial environments Prior to undertaking any work...

Страница 8: ...with signal or audio cables and reduce the possibility of interfer ence Warning Observe the polarity of incoming power supply cables Maximum cable section supported by the unit are Solid 4 0 mm2 Stra...

Страница 9: ...Vw2 Beacon power input Accepted beacon voltages are as follows if other voltages are required please contact your local Eaton representative 48 V dc 110 V ac 240 V ac Maximum cable section supported...

Страница 10: ...maximum allowable peak surge current is limited to 100 A by the on board relays The unit is fitted with a pair of 10 A 10 x 38 mm Mersen fuses part number S218194 Warning Only replace fuses with origi...

Страница 11: ...and contains system activity information from the 2Mx central controller and Vw2 status and activity going to the 2Mx 5 2 Basic operation Each output port can be configured to activate on any active...

Страница 12: ...nfigurable via SAS application A detailed description of all the configuration options is included in SAS Product Manual but some of the options are worth mentioning here for clarity and completion 6...

Страница 13: ...roved firmware The Sonix Vw2 units are controlled by a Microsemi ProASIC3 FPGA with instant on technology for fast and reliable operation To ensure correct operation of the unit it is supplied fully t...

Страница 14: ...ton and SONIX are registered trademarks All other trademarks are property of their respective owners Changes to the products to the information contained in this document and to prices are reserved so...

Отзывы: