SONIX VW2 TECHNICAL MANUAL  

TM368 / A  May 2022  www.eaton.com

4.7.4  Wiring multi-coloured beacon sets

The Vw2 can support a ‘common neutral’ wiring mode 

to reduce cabling costs when used with multicoloured 

beacon clusters.

Figure 9 - Common neutral wiring

Warning:

 Only common return paths on a single 

Vw2, do not bridge across multiple units.

Warning:

 The common return cabling must 

be sized to support the full load of all beacons 

illuminated.

4.7.5  Beacon loop wiring sizing

The beacon wiring should be sized to match the total 

steady state load while also compensating for any 

voltage drop over distance.

5  Unit operation

5.1  Data communications

The Beacon Bus provides a data control feed from and 

status replies to the 2Mx. The feed is a self-healing loop 

where data is being transmitted in both directions, to 

ensure that in the unlikely event of a cable failure there 

will be no loss in coverage. The Beacon Bus is a data 

connection bus only and carries no audio signal.

The Vw2 can receive and reply on either Top or Bottom 

ports depending on which is active. The protocol used is 

proprietary Sonix datagram format and contains system 

activity information from the 2Mx central controller and 

Vw2 status and activity going to the 2Mx.

5.2  Basic operation

Each output port can be configured to activate on 

any active PA/GA alarms, 1 to 6. When any alarms 

associated with an output are active on the PA/GA 

system, the output will activate.

Key settings: 

Loop 1 Alarm Map 

1 to 6

Loop 2 Alarm Map 

1 to 6

5.2.1  Alarm escalation

The Vw2 can be configured to extinguish the associated 

beacon if a higher priority alarm is active. 

This option is typically used when there are multi-

coloured beacon stacks and operators require only the 

highest priority to be active.

Key settings: 

Alarm Escalate   

Enabled

5.2.2  Emergency speech

Each output port can also be configured to activate 

when Emergency Speech (also called Important 

Message) is active on the PA/GA system. If enabled, 

the beacon output will also activate during an active 

Emergency speech broadcast whatever the alarm 

situation.

It is acceptable to configure an output to only be active 

on Emergency Speech and have no associated alarms.

ote: 

N

This setting ignores Alarm Escalation and so it is possible to have 

both alarm escalation enabled AND activate all beacons on Emergency 

Speech broadcasts.

Key settings:

Loop 1 Important Message 

Enabled

Loop 2 Important Message 

Enabled

L / +

N / -

E

L / +

N / -

E

L / +

N / -

E

L / +

N / -

E

L / +

N / -

E

J1

J6

Содержание SONIX Vw2

Страница 1: ...SONIXTM Vw2 Termination Unit SonixTM Vw2 Technical Manual...

Страница 2: ...for a particular purpose or merchantability other than those Specifically set out in any existing contract between the parties Any such contract states the entire obligation of eaton The contents of t...

Страница 3: ...feedback 2Mx Sonix 2Mx Central controller Amp 350 d Sonix 350 W Power Amplifier with 100 V line output Eol1 Sonix Remote End of Line unit Eol8 Sonix Amplifier to 100 V line interface unit 8 channel SP...

Страница 4: ...9 4 5 1 Connecting Vw2 within standalone or A B systems 9 4 5 2 Connecting Vw2 within N 1 systems 9 4 6 Beacon power input connection 9 4 6 1 Automatic redundant power switchover 9 4 7 Beacon output...

Страница 5: ...L SIMPLIFIED VIEW OF VW2 UNIT 7 FIGURE 2 DC POWER CONNECTIONS 8 FIGURE 3 SINGLE VW2 BUS CONNECTIONS 9 FIGURE 4 MULTIPLE VW2 CONNECTIONS 9 FIGURE 5 VW2 BEACON POWER INPUT 9 FIGURE 6 REDUNDANT POWER SWI...

Страница 6: ...controller i e it receives data packets acts on that data and sends a response back to the 2Mx The robust and industrial design of the module ensures its protection against open and short circuit ass...

Страница 7: ...u remain safe throughout During this work you may be exposed to potentially hazardous voltages currents confined spaces and potentially hazardous industrial environments Prior to undertaking any work...

Страница 8: ...with signal or audio cables and reduce the possibility of interfer ence Warning Observe the polarity of incoming power supply cables Maximum cable section supported by the unit are Solid 4 0 mm2 Stra...

Страница 9: ...Vw2 Beacon power input Accepted beacon voltages are as follows if other voltages are required please contact your local Eaton representative 48 V dc 110 V ac 240 V ac Maximum cable section supported...

Страница 10: ...maximum allowable peak surge current is limited to 100 A by the on board relays The unit is fitted with a pair of 10 A 10 x 38 mm Mersen fuses part number S218194 Warning Only replace fuses with origi...

Страница 11: ...and contains system activity information from the 2Mx central controller and Vw2 status and activity going to the 2Mx 5 2 Basic operation Each output port can be configured to activate on any active...

Страница 12: ...nfigurable via SAS application A detailed description of all the configuration options is included in SAS Product Manual but some of the options are worth mentioning here for clarity and completion 6...

Страница 13: ...roved firmware The Sonix Vw2 units are controlled by a Microsemi ProASIC3 FPGA with instant on technology for fast and reliable operation To ensure correct operation of the unit it is supplied fully t...

Страница 14: ...ton and SONIX are registered trademarks All other trademarks are property of their respective owners Changes to the products to the information contained in this document and to prices are reserved so...

Отзывы: