SONIX HMI-5 TECHNICAL MANUAL  

TM373 / A  June 2022  www.eaton.com

The available zone maps are:

Default Routine Speech

Set on a project level, typically into Process/

External areas 

Default Emergency 

Speech

Typically set to All-Call

Zone map Button(s)

Configured to cover a sub-set of available zones 

(Multiple buttons are allowed)

Alarm activations

Set to All-Call

5.6.3  Microphone input

The microphone input on the Hmi-5 can be either a fl ush 

mounted microphone on the chassis or a Hand-Held 

microphone on a fl exible coiled lead. 

The fl ush mount microphone is intended to be used 

from between 8 and 12 cm from the user whereas the 

Hand-Held microphone is intended to be held close to 

the talker, in the 4-8 cm range.

Figure 7 - Suggested microphone positioning

The microphone sensitivity can be adjusted on request, 

please contact your local Eaton representative.

5.6.4  Routine speech

A Routine speech broadcast is activated by pressing the 

Push to Talk (PTT) button, either on the unit or in the 

case of a Hand-Held microphone the PTT button is on 

the microphone itself.

5.6.4.1  Routine Chime

The Hmi-5 can be confi gured to play one of three 

different chimes before each routine speech broadcast, 

the chimes are referred to as single, double and triple 

bong. Selection of a chime creates a delay between 

activating PTT and routing voice to the PA/GA system 

while the chime plays.

Chime Name

Sound

Notes

Single Bong

660Hz decaying gong 

over ~4seconds

The decaying gongs have the 

new gong superimposed over 

the top after ~1.1s

Double Bong

660Hz then 550Hz 

decaying gongs over 

~5.5seconds

Triple Bong

660Hz then 550Hz then 

400Hz decaying gongs 

over ~7seconds

None

No chime

No chime is generated, and 

voice is routed to the system 

without delay

Table 3 - Available Routine Speech Chimes

Chime can be disabled for routine speech broadcasts.

5.6.4.2  PTT Timeout

The audio system on the Hmi-5 can be confi gured to 

have a maximum transmit time, called PTT Timeout. 

When this setting is active the access panel will cancel 

the active PTT session if it exceeds the time set in the 

confi guration. Valid values range from 30 seconds to 120 

seconds with no timeout also an option.

If this timeout event occurs, the Hmi-5 access panel 

will also generate a PTT Timeout fault. This can be 

used to identify situations where the PTT button has 

been accidentally depressed or no longer functioning 

correctly.

The PTT timeout fault can be disabled in confi guration.

5.6.5  Emergency speech

Emergency speech, sometimes referred to as Important 

Message, is a method for increasing the priority 

of a speech broadcast, combined with a different 

announcement tone. Within the Sonix PA/GA system 

emergency speech is the only way to broadcast 

speech over an active alarm. Flagging a broadcast as an 

Important message increases its priority.

Emergency speech is selected by pressing the 

Important Message button, this button is a toggle 

button with timeout. The timeout is ~30 seconds since 

the feature was activated or since the last Emergency 

speech broadcast from the access panel fi nished. 

Hmi-5 Certification

Label 

240.0mm

110.0mm

Ø6.0mm

2

1

2

8 – 12 cm

Содержание SONIX Hmi-5

Страница 1: ...SONIXTM Hmi 5 Ex Access Panel SonixTM Hmi 5 Technical Manual...

Страница 2: ...S FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF...

Страница 3: ...s feedback 2Mx Sonix 2Mx Central controller Amp 350 d Sonix 350 W Power Amplifier with 100 V line output Eol1 Sonix Remote End of Line unit Eol8 Sonix Amplifier to 100 V line interface unit 8 channel...

Страница 4: ...ensions 9 3 2 Power and utility 9 4 INSTALLATION AND CONNECTIVITY 10 4 1 Mounting 10 4 2 Glanding 10 4 3 Data and Audio connections 10 4 3 1 Local Mute Local Attenuate unit 10 4 3 2 Local Power 10 4 3...

Страница 5: ...5 6 3 Microphone input 16 5 6 4 Routine speech 16 5 6 4 1 Routine Chime 16 5 6 4 2 PTT Timeout 16 5 6 5 Emergency speech 16 5 6 5 1 Emergency speech chime 17 5 6 6 PTT Release Delay 17 5 6 7 Mute Outp...

Страница 6: ...S 10 FIGURE 4 B SIDE DATA AND AUDIO CONNECTIONS 10 FIGURE 5 BUTTON FLAP GUARD OPERATION 12 FIGURE 6 PA GA SYSTEM BROADCAST PRIORITY 15 FIGURE 7 SUGGESTED MICROPHONE POSITIONING 16 LIST OF TABLES TABLE...

Страница 7: ...products we provide adequate packaging to protect the goods during transit Please ensure that once unpacked checked and installed that all packaging is disposed recycled in a responsible manner 1 3 E...

Страница 8: ...ions including Alarms 1 6 Alarm Cancel Alarm Attenuate Routine speech With pre set zoning Emergency speech All Call or with pre set zone control Zone buttons LED Lamp test Unit self monitoring and fau...

Страница 9: ...outside the hazardous area the Hmi 5 shall not be used without the Hmi Br Use of the Hmi 5 without connection of the Hmi Br invalidates the type of protection stated within this certificate Installati...

Страница 10: ...ance that the system can support for an Hmi 5 is 300 m connections longer than this are not supported and are likely to result in un reliable operation Connections to a Sonix Hmi Barrier should be wir...

Страница 11: ...y The Hmi 5 implements different electrical interface to the Sonix Hmi 26 access panel and this requires a hardware link change on the Hmi Tu see Hmi Tu manual for details 5 2 A B duplication The Soni...

Страница 12: ...D indicator opening the button to change the LED can adversely affect the rating Please contact your local Eaton representative for guidance on this matter The buttons have optional fitted by default...

Страница 13: ...Zone s are pre selected by the local panel PTT not active Solid Associated Zone s are selected by the local panel may or not be broadcasting 5 4 6 Alarm activation Alarm activation buttons can be set...

Страница 14: ...5 4 11 Local Attenuate Local attenuate is a toggle action function it can be used at any point to reduce the output of the local loudspeaker s Typically Local Attenuate will be implemented with a pre...

Страница 15: ...ated alarm Solid System has an active auto initiated alarm 5 6 Making a speech broadcast Speech broadcasts on Sonix systems are made of up three parts the audio from the user see section 6 6 3 a prior...

Страница 16: ...g over 4seconds The decaying gongs have the new gong superimposed over the top after 1 1s Double Bong 660Hz then 550Hz decaying gongs over 5 5seconds Triple Bong 660Hz then 550Hz then 400Hz decaying g...

Страница 17: ...is the active PTT broadcast on the PA GA system This approach allows the user to hear any overriding broadcasts if they are not the one active on the system 5 6 7 1 Attenuate output Additionally the H...

Страница 18: ...ta connection cable are required Please see the SAS user manual for more details 6 4 1 Ping set Set new Unit ID ote N It is likely that multiple persons will be required due to limited time window to...

Страница 19: ...or guidance on this matter The LED indicators fitted to the Sonix Hmi 5 are long life units designed not to be replaced within the typical lifespan of the unit If it becomes necessary to change the in...

Страница 20: ...d there is potential for damage to the unit Procedure for programming units is as follows 1 Visual inspection of unit to ensure no damage to PCB and components 2 Connect power to A side of unit using...

Страница 21: ...Sonix Hmi 5 Technical Manual 21 SONIX HMI 5 TECHNICAL MANUAL TM373 A June 2022 www eaton com THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 22: ...aton and SONIX are registered trademarks All other trademarks are property of their respective owners Changes to the products to the information contained in this document and to prices are reserved s...

Отзывы: