SONIX HMI-5 TECHNICAL MANUAL  

TM373 / A  June 2022  www.eaton.com

5.4.8  Alarm Attenuate

Alarm attenuate is a toggle action function, it will only 

latch on if an Alarm is active on the PA/GA system. 

The alarm attenuate action operates at a system level, 

activating this button toggles the current system state 

independent of the access panel.

If assigned to a standard button the associated indictor 

has the following states:

Off

Alarm Attenuate is not active 

Fast flashing (5 Hz)

Alarm Attenuate is changing state

Solid

Alarm Attenuate is active

5.4.9  Alarm Inhibit

Alarm Inhibit is used to prevent automated activation 

of alarms from external systems such as Fire & Gas. 

It does not prevent manual activation from any access 

panel.

If assigned to a standard button the associated indictor 

has the following states:

Off

Alarm Inhibit is not active 

Fast flashing (5 Hz)

Alarm Inhibit is active on the system

Solid

Alarm Inhibit is active locally

ote: 

N

Not a recommended action for an Hmi-5 access panel. Eaton 

recommends that a key switch connected to Sonix Io would be a more 

rigorous solution.

5.4.10  Ms12 message initiation

Initiation of a pre-recorded message from the Ms12. The 

message can only be initiated if it is loaded (recorded) 

and enabled on the Ms12.

If assigned to a standard button the associated indictor 

has the following states:

Off

Button is not active 

Fast flashing (5 Hz)

Button is active, message playback requested

ote: 

N

There is no success/failure feedback to the user on the access 

panel.

5.4.11  Local Attenuate

Local attenuate is a toggle action function, it can be 

used at any point to reduce the output of the local 

loudspeaker(s).

Typically, Local Attenuate will be implemented with a 

pre-set timeout window to prevent permanent latch up, 

values between 5 and 30 minutes.

 

If assigned to a standard button the associated indictor 

has the following states:

Off

Local Attenuate is not active 

Fast flashing (5 Hz)

Local Attenuate is changing state soon

Solid

Local Attenuate is active

5.4.12  Background Music control

Background music is an optional feature of the Sonix PA/

GA system, its management and control are not covered 

in this manual. Please the 2Mx and SAS manuals for 

more information.

BGM control is a change state request action function 

that allows remote control of BGM. It requires a number 

of Sonix components to be correctly configured to work.

If assigned to a standard button the associated indictor 

has the following states:

Off

Button is not active  

Solid

Button is active, BGM state change requested

ote: 

N

There is no success/failure feedback to the user on the access 

panel.

ote: 

N

Replaces Local Attenuate, cannot be used together.

5.5  Indication only options

Any of the features above with indicator states can be 

used as an indicator only with the push button disabled 

in configuration. 

The following are options for using a button as indication 

only without any on-press event associated.

5.5.1  System busy

System busy indicator is used to show when the system 

has active. 

If assigned to a standard button the associated indictor 

has the following states:

Off

System is currently idle

Fast flashing (5 Hz)

Engineers panel active on the system

Solid

System is busy with an Alarm, Routine or 

Emergency speech

Содержание SONIX Hmi-5

Страница 1: ...SONIXTM Hmi 5 Ex Access Panel SonixTM Hmi 5 Technical Manual...

Страница 2: ...S FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF...

Страница 3: ...s feedback 2Mx Sonix 2Mx Central controller Amp 350 d Sonix 350 W Power Amplifier with 100 V line output Eol1 Sonix Remote End of Line unit Eol8 Sonix Amplifier to 100 V line interface unit 8 channel...

Страница 4: ...ensions 9 3 2 Power and utility 9 4 INSTALLATION AND CONNECTIVITY 10 4 1 Mounting 10 4 2 Glanding 10 4 3 Data and Audio connections 10 4 3 1 Local Mute Local Attenuate unit 10 4 3 2 Local Power 10 4 3...

Страница 5: ...5 6 3 Microphone input 16 5 6 4 Routine speech 16 5 6 4 1 Routine Chime 16 5 6 4 2 PTT Timeout 16 5 6 5 Emergency speech 16 5 6 5 1 Emergency speech chime 17 5 6 6 PTT Release Delay 17 5 6 7 Mute Outp...

Страница 6: ...S 10 FIGURE 4 B SIDE DATA AND AUDIO CONNECTIONS 10 FIGURE 5 BUTTON FLAP GUARD OPERATION 12 FIGURE 6 PA GA SYSTEM BROADCAST PRIORITY 15 FIGURE 7 SUGGESTED MICROPHONE POSITIONING 16 LIST OF TABLES TABLE...

Страница 7: ...products we provide adequate packaging to protect the goods during transit Please ensure that once unpacked checked and installed that all packaging is disposed recycled in a responsible manner 1 3 E...

Страница 8: ...ions including Alarms 1 6 Alarm Cancel Alarm Attenuate Routine speech With pre set zoning Emergency speech All Call or with pre set zone control Zone buttons LED Lamp test Unit self monitoring and fau...

Страница 9: ...outside the hazardous area the Hmi 5 shall not be used without the Hmi Br Use of the Hmi 5 without connection of the Hmi Br invalidates the type of protection stated within this certificate Installati...

Страница 10: ...ance that the system can support for an Hmi 5 is 300 m connections longer than this are not supported and are likely to result in un reliable operation Connections to a Sonix Hmi Barrier should be wir...

Страница 11: ...y The Hmi 5 implements different electrical interface to the Sonix Hmi 26 access panel and this requires a hardware link change on the Hmi Tu see Hmi Tu manual for details 5 2 A B duplication The Soni...

Страница 12: ...D indicator opening the button to change the LED can adversely affect the rating Please contact your local Eaton representative for guidance on this matter The buttons have optional fitted by default...

Страница 13: ...Zone s are pre selected by the local panel PTT not active Solid Associated Zone s are selected by the local panel may or not be broadcasting 5 4 6 Alarm activation Alarm activation buttons can be set...

Страница 14: ...5 4 11 Local Attenuate Local attenuate is a toggle action function it can be used at any point to reduce the output of the local loudspeaker s Typically Local Attenuate will be implemented with a pre...

Страница 15: ...ated alarm Solid System has an active auto initiated alarm 5 6 Making a speech broadcast Speech broadcasts on Sonix systems are made of up three parts the audio from the user see section 6 6 3 a prior...

Страница 16: ...g over 4seconds The decaying gongs have the new gong superimposed over the top after 1 1s Double Bong 660Hz then 550Hz decaying gongs over 5 5seconds Triple Bong 660Hz then 550Hz then 400Hz decaying g...

Страница 17: ...is the active PTT broadcast on the PA GA system This approach allows the user to hear any overriding broadcasts if they are not the one active on the system 5 6 7 1 Attenuate output Additionally the H...

Страница 18: ...ta connection cable are required Please see the SAS user manual for more details 6 4 1 Ping set Set new Unit ID ote N It is likely that multiple persons will be required due to limited time window to...

Страница 19: ...or guidance on this matter The LED indicators fitted to the Sonix Hmi 5 are long life units designed not to be replaced within the typical lifespan of the unit If it becomes necessary to change the in...

Страница 20: ...d there is potential for damage to the unit Procedure for programming units is as follows 1 Visual inspection of unit to ensure no damage to PCB and components 2 Connect power to A side of unit using...

Страница 21: ...Sonix Hmi 5 Technical Manual 21 SONIX HMI 5 TECHNICAL MANUAL TM373 A June 2022 www eaton com THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 22: ...aton and SONIX are registered trademarks All other trademarks are property of their respective owners Changes to the products to the information contained in this document and to prices are reserved s...

Отзывы: