System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
33
► To enable Fast Charge (or to stop Fast Charge manually)
•
Use the SC300 keypad to go to:
Control Processes > Fast Charge
.
•
Or, in Web go to:
Control Processes >
Fast Charge
.
Information
The following information is available about Fast Charge.
Parameter
Description
Where to find:
State
Indicates if Fast Charge is Disabled, Active,
Inactive or Pending.
SC300: Control Processes >
Fast Charge
DCTools/Web: Control
Processes > Fast Charge
Ah Discharged
The current level of battery discharge. A Fast
Charge cycle is started if this value is above the
Ah Threshold.
See also Reset Battery State on page 76.
Maximum Time
Remaining
The maximum time to the end of the currently
active Fast Charge.
Voltage Offset
The adjustment to the bus voltage being applied
due to the Fast Charge.