Communications
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
111
Test Emails can be sent to test the Email Communication setup.
► To send a test Email:
1
On the web, go to
System > Interfaces > Remote Access Protocols > Email Notifications
.
2
In DCTools, go to
Communications > Remote Access Protocols >
Email Notifications
.
3
Click the
Send Test Email
button on the row of the Email address to be tested.
► Diagnostics
1
On the web, go to
System > Interfaces > Remote Access Protocols > Email Notifications
.
2
In DCTools, go to
Communications > Remote Access Protocols >
Email Notifications
.
3
The result of the most recent SMTP operation affecting each recipient is shown on the row
containing the recipient's Email address. The last three digits represent the SMTP reply codes
defined in RFC 821 and its extensions. A code of 250 indicates that the most recent email was
delivered successfully. The SC300 will set the result to 9999 if communication with the SMTP
server has failed.
Modbus-TCP Communications
The SC300 can be configured to accept Modbus queries and commands from a Modbus
Building Management System or other Modbus master.
For details of the Modbus registers supported by the SC300, please request Application Note
AN0107 from your Eaton dc product supplier.
Modbus-TCP* Connections
The SC300 can accept one or more Modbus connections on the reserved Modbus-TCP port of
502.
1.
SC300 system controller
2.
PC/laptop with Building Management System
using Modbus-TCP.
3.
Communications network. Protocol: TCP/IP