Installation
S801+ Soft Starter
MN03900002E—November 2012
www.eaton.com
17
Basic Connection Diagram for 2-Wire Pushbutton
Notes
1.
A minimum wire of 14 AWG (2.5 mm
2
) should be used
between the control power supply and the control
terminal block.
2.
See Using an Auxiliary Relay section below if it is desired
to use a relay instead of an indicating lamp for terminals
13, 14, 95, 96 and 98.
3.
120 Vac may be applied to terminals 13, 14, 95, 96,
and 98.
4.
Add ferrite, Fair-Rite #0446176451 to DC Power Leads
and Control I/O Leads (all through one ferrite) at S801+.
5.
Auxiliary relays: 3 amps at 120 Vac or 24 Vdc, 10 amps
max. (resistive) switching.
E-Stop
(+) Us 24 Vdc
(-) Us
Reset
Local
Start/Run
Maintained
Momentary
Ferrite
Aux Relays
-24V
+24V
Permissive
Start
Jog
Disable Ovld
Reset
98
96
95
14
13
4
3
2
1
P
+
-