General Information
S801+ Soft Starter
MN03900002E—November 2012
www.eaton.com
49
11
Overload Fault
Motor overloaded for an extended period of
time.
Reduce the motor’s load.
Thermal Memory is over 100%
Verify the
Overld Trip FLA
and/or
Ovrld Trip Class
for proper
adjustment.
Note: Exceeding nameplate ratings will shorten equipment life.
Fault during motor start: Verify system is not exceeding the specified
maximum starts per hour.
Increase the initial torque and/or reduce ramp time to bring the motor
up to speed faster.
Increase Trip Class setting (30 maximum) and/or reduce ramp time
setting.
Notes:
Higher than normal thermal memory may indicate an abnormal operating condition and signal an impending
Overload
fault.
12
Motor Stall
Motor not at rated RPM at end of start ramp
time and/or current is in excess of 2X FLA.
Lengthen
Soft Start Time
and/or increase
Initial Torque
potentiometers
Bypass contactors not closed at the end of
the start time (start current low/ramp time
short).
Loads that are heavily loaded (high inertia) during a start such as fans
will often need an initial torque setting much greater than the factory
default.
Set
Kick Start
parameters.
Notes:
Motor rpm is monitored for a synchronous speed condition. A Motor Stall fault will occur at the end of the ramp time (default is 20 seconds) if the
motor is not at synchronous speed and the current is in excess of 2X FLA. This feature is not user settable. Verify that the motor is properly sized
for the load.
13
Jam
Soft Starter in Bypass: Motor below rated
RPM and/or current exceeds 3X FLA.
Remove obstruction.
Verify proper FLA setting in Protections Menu.
Jam Fault can be disabled if trips occur during normal operation (Over
Current Fault will provide protection at a higher current threshold of
4X catalog FLA).
Notes:
The Jam Fault may be disabled (not recommended). The maximum RMS value of the 3 phase currents is monitored when the internal bypass
contactors are closed.
The Jam Fault Trip threshold is 3X Motor FLA and is not user settable.
14
Motor Voltage Phase
Reversal
Incoming line phase rotation sequence
opposite of device setting.
Exchange two incoming mains phases.
One phase missing and/or open fuse or
breaker.
Verify that all circuit breakers are closed or fuses are serviceable.
Notes:
If mains leads need to be changed, swap incoming leads and set
Phase Sequence
to match incoming sequence. If an upstream reverser is used,
disable
Phase Rev Fault (not recommended)
. This fault is not uncommon in new installations. In the event of a blown fuse prior to a START
command, this fault may occur as the unit is not able to determine phase rotation with one open fuse. If motor rotation requires exchange of
phases, exchange the cables between the soft starter and the motor.
S801+ Fault Codes, continued
Code
Fault
Condition
Solution
Содержание S801+ Series
Страница 1: ...S801 Soft Starter User Manual Effective November 2012 New Information...
Страница 11: ...S801 Soft Starter x S801 Soft Starter MN03900002E November 2012 www eaton com...
Страница 65: ...General Information 54 S801 Soft Starter MN03900002E November 2012 www eaton com...
Страница 66: ...General Information S801 Soft Starter MN03900002E November 2012 www eaton com 55...
Страница 67: ...General Information 56 S801 Soft Starter MN03900002E November 2012 www eaton com...