Copyright © 2018 Eaton’s Crouse-Hinds Division

IF 1688 • 08/18

Page 5

Section 7: Contact Insertion Instructions (excluding single pole)

Copyright © 2018 Eaton’s Crouse-Hinds Division

IF 1688 • 08/18

Page 6

1. 

Locate position No. 1 on back of insert (1).

2. 

Take correct numbered contact (2) (see step 4, Section 

6) and insert into position 1, pushing by hand until 

feeling resistance. Complete installation by using correct 

insertion tool (3) per Table 5 to press contact (2) until 

hearing and feeling the contact “click” into place.

3. 

Repeat steps 1 & 2 for each location # on the insert (1). 

WARNING: Even if a location is not being used, a blank 

pin/socket must be inserted to maintain environmental 

integrity.

Section 8: Crimping Instructions for Single Pole Contacts

A. Crimping Instructions:

1. 

Prepare cable, cutting to length as needed.

2. 

Strip outer jacket to length per Table 1.

3. 

Take crimping tool per Table 4 and install correct die based on 

pin size being crimped.

4. 

Place stripped end of conductor into contact socket, verify that 

between 1 and 3 mm of bare copper is exposed between end 

of contact and insulation.

5. 

Place contact with wire into crimping tool, aligning die faces 

with 1st set (see picture) of alignment marks.  

6. 

Operate tool until the contact is crimped and tool releases.

7. 

Move crimped contact to 2nd set (see picture) of alignment 

marks and repeat step 6.

1st Set Alignment Marks

2nd Set Alignment Marks

Section 9: Maximum Allowable Amperage Calculation

Shell 

size

Max. wattage   
40°C ambient 

90°C rated wire

Max. wattage   
40°C ambient 

110°C rated wire

Max. wattage   
40°C ambient 

125°C rated wire

12

12.8

13.2

13.2

16

20.7

27.4

28.9

20

23.6

31.1

33.1

24

35.6

46.8

49.7

28

22.1

28.9

33.2

Table A. Maximum Current and Resistant Values

Pin size

Max. current 

(A)

Resistance 

(ohms)

23 AWG

1 AMP

0.0218

16 AWG

18 AMP

0.0053

13 AWG

26 AMP

0.0028

12 AWG

30 AMP

0.0021

10 AWG

40 AMP

0.0013

8 AWG

55 AMP

0.00086

4 AWG - 

Pressure

90 AMP

0.00056

4 AWG - 

Crimp

95 AMP

0.00036

1/0

155 AMP

0.00032

4/0

225 AMP

0.00018

313 MCM

636 AMP

0.0000515

444 MCM

796 AMP

0.0000414

535 MCM

898 AMP

0.0000374

777 MCM

1135 AMP

0.0000254

Table B. Maximum Heat Dissipation Per Connector

Maximum total amperage per shell is limited by the 

temperature threshold of the internal components. Maximum 

amperages in Table A may change when multiple contacts are 

used in one shell. If using multiple conductors, the dissipated 

heat [watts] should not exceed the levels in Table B. The 

formula below can be utilized to calculate dissipated heat. 

WARNING

SHOCK HAZARD

Note: Maximum heat dissipation levels calculated at max. 
ambient temperature rating of 40°C.

Formula:

  

D: Total heat dissipation per shell [watts]

 

W: Total heat dissipation per set of contacts of the 

same size / gauge [watts] and same current [amps]

 

I: Expected current per contact not to exceed the 

max. current outlined in Table A [amps]

 

R: Contact resistance [ohms]

N: Number of conductors

  

 

D: W1 + W2 + W3 + … Wn

 

W = I^2 x R x N

 

D ≤ Watt Values (Table 2)

Section 10: Table References 

1. Insert

2. Contact

3. Insertion Tool

1. 

Locate the conductor and related contact.

2. 

Insert conductor into the opened termination side 

of the contact.

3. 

Tighten screw to torque value shown in Table 6.

4. 

Repeat for all contacts.

Mod II (Crimp Style)

Mod I (Pressure Style)

Table 1. Conductor Strip Lengths

Contact size

Conductor strip length

AWG

(mm

2

 eqv.)

inches

mm

23

0.26

0.586

12.88

16

1.3

0.586

12.88

13

2.62

0.585

12.85

12

3.3

0.585

12.85

10

5.3

0.668

14.96

8

8.4

0.839

19.30

4

22

0.896

22.76

1/0

53

1.417

35.99

4/0

107

1.425

36.20

313 MCM

159

1.85

44.45 

444 MCM

227

1.85

44.45

535 MCM

273

1.85

44.45

777 MCM

394

1.85

44.45

Содержание Roughneck IF 1688

Страница 1: ...uare Flange Receptacle A To disassemble female inline receptacle 1 Place cable adapter 1 in rubber or aluminum jawed vice Unscrew female skirt 2 left hand thread from cable adapter 1 keeping environme...

Страница 2: ...to prevent strain on the wire terminals 3 Fully tighten wrench 4 If using mechanical clamp tighten cord grip screws to torque found on Table 3 Retaining Clip Brass Washer 7 Bushing 1 Cable Adapter 4...

Страница 3: ...m Current and Resistant Values Pin size Max current A Resistance ohms 23 AWG 1 AMP 0 0218 16 AWG 18 AMP 0 0053 13 AWG 26 AMP 0 0028 12 AWG 30 AMP 0 0021 10 AWG 40 AMP 0 0013 8 AWG 55 AMP 0 00086 4 AWG...

Страница 4: ...t no 8 CH 2 8250 CH 1265 10 CH 2 8250 CH 1205 12 CH 2 8250 AT 1000 12 16 CH 2 8250 AT 1000 16 IF 1688 08 18 Table 2 External Cable Jacket Strip Length Jacket strip length culti conductor cable Standar...

Страница 5: ...anco y coloque el borde hembra 2 en el tornillo de banco sujete por la cubierta protectora 3 con la etiqueta de advertencia hacia abajo B Para conectar un cable al recept culo hembra integrado 1 Pase...

Страница 6: ...a torsi n indicada en la Tabla 3 Abrazadera de retenci n Arandela de lat n B Para conectar el conector macho a la cubierta de aislamiento 1 Deslice la malla c nica 8 o la pinza mec nica 9 el adaptador...

Страница 7: ...ntactos m ltiples en el armaz n Si usa conductores m ltiples el calor disipado vatios no debe exceder los niveles indicados en la Tabla B La f rmula a continuaci n se puede usar para calcular el calor...

Страница 8: ...CH 2 8250 AT 1000 16 IF 1688 08 18 Tabla 2 Longitud de la camisa de cable desprovista Longitud de la camisa desprovista Cable de conductores m ltiples Adaptador Corto Adaptador Largo pulgadas mm pulga...

Страница 9: ...7 et l adaptateur de c ble 1 D gagez le c ble de mani re avoir une longueur suffisante pour travailler confortablement 2 Pr parez le c ble et chaque conducteur individuel conform ment aux instruction...

Страница 10: ...ironmental Cover 9 Mechanical Clamp 8 Basket Weave 9 Retaining Clip 8 Brass Washer 11 Insulator Housing 7 Male Contact B Pour brancher le contact m le au bo tier isolant faites ceci 1 Faites glisser l...

Страница 11: ...rs contacts sont utilis s dans une m me coquille Lorsqu un c ble multipolaire est utilis la chaleur dissip e watts ne devrait pas d passer les valeurs indiqu es dans le tableau B Utilisez la formule c...

Страница 12: ...2 16 CH 2 8250 AT 1000 16 IF 1688 08 18 Tableau 2 Longueur de d nudage de la gaine ext rieure du c ble Longueur de d nudage de la gaine ext rieure c ble multipolaire Adaptateur Court Adaptateur Longue...

Отзывы: