4 Commissioning
4.4 Acyclic data
36
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
4.4.3 List of parameters
Table 10:
List of parameters
PNU index
PNU subindex
Access
right
Data
type
Meaning
Display
number
Value Range
Description
1
0
ro
N2
Frequency reference value/Motor
shaft speed
P00-03
-16384 - 16384
4000
hex
= 100 %, 100 % = P-01
5
1
rw
N2
Preset speed 1
P-20
-16384 - 16383
4000
hex
= 100 %, 100 % = P-01
5
2
rw
N2
Preset speed 2
P-21
-16384 - 16383
4000
hex
= 100 %, 100 % = P-01
5
3
rw
N2
Preset speed 3
P-22
-16384 - 16383
4000
hex
= 100 %, 100 % = P-01
5
4
rw
N2
Preset speed 4
P-23
-16384 - 16383
4000
hex
= 100 %, 100 % = P-01
20
1
rw
U16
Maximum speed limit
P-01
0 - 5xP-09
3000
≙
50 Hz
20
0
rw
U16
Minimum speed limit
P-02
0 - P-01
3000
≙
50 Hz
21
0
rw
U16
Skip frequency band width
P-26
0 - P-01
3000
≙
50 Hz
22
0
rw
U16
Skip frequency / center point
P-27
0 - P-01
3000
≙
50 Hz
23
0
rw
U16
Adaptation voltage
U/f characteristic curve
P-28
0 - P-07
Details in Volt
24
0
rw
U16
Adaptation frequency U/f
characteristic curve
P-29
0 - P-09
Details in Hz
27
0
rw
U16
Boost
P-11
FS1 0 - 200
FS2 0 - 150
FS3 0 - 100
100
≙
10 %
28
0
rw
Boost frequency
P-32
Only available with alternating
current motor types
29
0
rw
Boost time
P-33
Only available with alternating
current motor types
111
0
rw
T2
Acceleration ramp time
P-03
0 - 600
0 - 6000
300
≙
3.00 s
114
0
rw
T2
Deceleration ramp time
P-04
0 - 600
0 - 6000
300
≙
3.00 s
116
0
rw
T2
Second deceleration ramp time
P-24
0 - 2500
250
≙
2.50 s
202
0
ro
Octet[3]
Variable frequency drive part no.
P00-20
String: e.g., “DC1“
203
0
rw
UInt16
HW version
Hardware version of the
variable frequency drive
203
1
rw
UInt16
HW version net
Hardware version of the SWD
Interfaces
206
1
ro
U16
Software version, control section
P00-18
103 = 1.03
206
0
ro
S16
Software version power section
P00-18
103 = 1.03
209
0
ro
Octet[11]
Variable frequency drive serial
number
P00-19
11 byte ASCII code
210
0
rw
U16
Rated motor current
P-08
0 - depending on
device
with one decimal point
e.g.14
≙
1.4 A
211
0
rw
U16
Nominal motor voltage
P-07
0 - 500
Details in Volt
Содержание PowerXL DX-NET-SWD
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...