4 Commissioning
4.3 Cyclic data
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
29
4.3.2 Profile 1 (8 bit): Inputs (status)
Input bytes 0 and 1 (Short) are mapped as follows on SmartWire-DT.
Table 6:
Profile 10: Input bytes 0 and 1
Byte
BIT
Designation
Meaning
0
0, 1
–
Not used
2, 3
A1, A2
1-0-A- switch on DX-NET-SWD:
00: not defined
10: Position A: Automatic (commands via SmartWire-
DT/control signal terminal)
01: Position 0: variable frequency drive stop
11: Position 1: variable frequency drive operation
4
DIAG
0: no diagnostic alarm
1: Diagnostic alarm present
5
–
Not used
6
PRSNT
0: Device not present
1: Device present
7
SUBST
0: Configured module present
1: Universal module M22-SWD-NOP(C) present
1
0
ERR
Error present
0: no error
1: Error
1
WARN
Warning present:
0: no warning
1: Warning
2
RDY
Ready, switched on:
0: not switched on
1: switched on
3
f = f-ref
Running at setpoint:
0: Ref. frequency not reached
1: Ref. frequency reached
4
f-Level
Actual speed is greater than the signaling threshold
0: Actual speed is less than or equal to the signaling
threshold
1: Actual speed is greater than the signaling
threshold
5
Q 1
Device Info Q1
6
Q2
Device Info Q2
7
Q3
Device Info Q3
Содержание PowerXL DX-NET-SWD
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...