4 Commissioning
4.4 Acyclic data
38
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
363
0
rw
UInt16
Modbus RTU Baud rate
P-36
0 - 6
2 : 9.6 kBit/s
3: 19.2 kBits/s
4: 38.4 kBits/s
5: 57.6 kBits/s
6: 115.2 kBits/s
363
1
rw
Uint16
CANopen baud rate
P-50
0 - 3
0: 125 kBit/s
1: 250 kBit/s
2: 500 kBit/s
3: 1000 kBit/s
381
0
rw
U16
Display scaling factor
P-40
0 - 6000
1000
≙
0.10
390
0
rw
U16
Output switching frequency
P-17
0 - 5
0: 4 kHz
1: 8 kHz
2: 12 kHz
3: 16 kHz
4: 24 kHz
5: 32 kHz
390
1
ro
U16
Switching frequency
P00-14
0 - 5
0: 4 kHz
1: 8 kHz
2: 12 kHz
3: 16 kHz
4: 24 kHz
5: 32 kHz
423
0
rw
U16
Digital input function selection
P-15
0 - 12
see table “Input functions“
451
0
rw
U16
Selection of the relay output func-
tion
P-18
0 - 7
0:RUN, enable (FWD, REV)
1: READY, ready for operation
2: output frequency = frequency
reference value
3 : Error message (variable
frequency drive not ready)
4 : Output frequency < limit
value (P-19)
5: Output current > limit value
(P-19)
6: Output frequency < limit
value (P-19)
7: Output current < limit value
(P-19)
452
0
rw
U16
Limit value for the relay output
control
P-19
0 - 1000
450 = 45.0 %
PN
U index
PN
U subindex
Access
right
Data
type
Meaning
Display
number
Value Range
Description
Содержание PowerXL DX-NET-SWD
Страница 4: ...II ...
Страница 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Страница 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...